1.Are among our most popular product
2.Easy to use
3.Can show leakage from the
4.fast shipping
5.Price RMB2
Power | DC12V-DC30V/AC9V--AC25V |
power consumption | <3W |
Operating temperature | 0 °C ~ 50 °C |
Operating Humidity | 10% ~ 90% RH; non-condensing |
Atmospheric pressure | 86 kpa ~ 106 kpa |
Overview
HW-1088 leak location monitoring module can monitor up to 1500 meters of BTR flooding sense lines, once the liquid is detected, it will locate leak location, leak through the LED display position value, and generate sound and light alarms; also through the RS485 interface, Will be sent to the control system leak case. HW-1088 using MODBUS RTU communication protocol and control system, user-HW-1088 will be integrated into different systems.
Features
Dual sensing line interface, up to 1500 meters with sensors monitoring
LED display alarm status and alarm channels
Four digital display leak location.
Built-in buzzer alarm, which realizes a local alarm.
Dual relay module provides two normally open / normally closed switch to an external alarm signal to extend the warning system.
Up to forty alarm log storage space, user query history alarm event.
12-30VDC/9V-25VAC a wide range of operating voltage.
simple twisted pair RS485 communication, communication distance up to 1000 meters.
Address software settings and parameters.
convenient DIN rail mounting