1 co2 split controller with LCD display
2 provide 3X analog outputs (0~10VDC)
3 RS485 communication interface
Gas sensor | Non-Dispersive Infrared Detector (NDIR) arbon Dioxide sensor |
Accuracy@25(77) | ±40ppm + 3% of reading (@22) |
Stability | <2% of FS over life of sensor (15 yr typical) |
Calibration interval | ABC_Logic Self Calibration |
Non linearity | <1% of FS |
Altitude calibration | Programmable from 0-9,900m in 100m increments |
Response Time | <2 minutes for 90% step change |
Signal update | Every 2 seconds |
Warm up time | 48 hours (first time) 10 minutes (normal operation) |
CO2 measuring range | 020,000ppm or 050,000ppmt selectable |
CO2 setting & Display resolution | 1ppm |
Temperature sensor | NTC |
Humidity sensor | HS series capacitive sensor |
Temperature dependence | 0.2% FS/ |
Temperature correction | Self compensation |
Temperature measuring/ setting range | 050(32122)/ 545(41113) |
Humidity measuring/setting range | 099%RH / 595%RH |
Relay outputs | 3Xrelay on/off outputs to control CO2 device/fan and humidity device and temperature device |
Analog outputs | 3Xanalog outputs (0~10VDC) to control CO2 device/fan and humidity device and temperature device |
Communication interface | RS-485, 19200(default) 15KV antistatic protection |
Flow rates | Diffusion version 80 ~ 120 cc/min |
Operation conditions | 0~50(32~122); 0~95%RH, non condensing |
Storage conditions | -40~70(-40~158) |
NDIR CO2 sensor lifetime | 15 years |
Power supply | 24VAC/24VDC |
Net weight | F2000ASC- CO2 -5003: 290g, F2000ASC- CO2 -5030: 250g F2000TSM- CO2-S301-N: 210g |
Dimensions | F2000ASC- CO2 -5003 130mm×90mm×40mm F2000ASC-CO2 5030 120mm×90mm×24mm F2000TSM- CO2-S301-N100mm×80mm×28mm |
Installment standard | 65mm×65mm or 2×4wire box |
Approval Standard | CE-Approval |
Selection of setup | DIP switch inside and button outside |