Be adopted front and rare construction for the permanent magnetic .
high reliability, long endurance free maintenance
VSM series of indoor high voltage vacuum circuit breaker is adopted front and rare construction for their permanent magnetic and vacuum interrupters. The main conducting circuit is with floor-standing type, the upper and lower outlet terminal and vacuum interrupters are installed in one insulation house. The insulation house is casted with epoxy resin material by APG technology, which can protect the surface of the vacuum interrupters against dust accumulation and impact. It also has good insulation property under humid, hot and pollution ambient condition.
The vacuum circuit breaker with permanent mechanism is air-insulated, used for indoor installation for different kind of power load, it is suitable for electrical net construction and reconstruction project in municipal net, rural net, mineral and railway net system, especially used in that fields which require frequently switching and have some requirement for short circuit operation cycles. This product was introduced by some international advance technique and processing technology with characteristics of intelligence, high reliability, long endurance and free maintenance etc.
Main Technical Specification
S.N | Name | Unit | Data | ||||||
1 | Rated voltage | kV | 12 | ||||||
2 | Rated current | A | 630 | 1000 1250 | 1600 2000 2500 3150 | ||||
3 | Rated short circuit breaking current | kA | 20 | 25 | 20 | 25 | 31.5 | 31.5 | 40 |
4 | Rated peak withstand current | kA | 50 | 63 | 50 | 63 | 80 | 80 | 100 |
5 | Rated short time withstand current | kA | 20 | 25 | 20 | 25 | 31.5 | 31.5 | 40 |
6 | Rated short circuit making current | kA | 25 | 63 | 25 | 63 | 80 | 80 | 100 |
7 | Switching operations of short circuit current | Cycle | 50 | 30 | |||||
8 | Rated operating sequence |
| 0-0.3s-CO-180s-CO,0-180s-CO-180s-CO(40kA) | ||||||
9 | Mechanical endurance | Cycle | 20000 | ||||||
10 | Rated breaking operations of the rated current | Cycle | 20000 | ||||||
11 | Rated lightning impulse withstand voltage | kV | 75 | ||||||
12 | Rated power frequency withstand voltage | kV/min | 42 | ||||||
13 | Contact stroke | mm | 11 1 | ||||||
14 | Overtravel of contacts | mm | 4 0.5 | ||||||
15 | Closing speed | m/s | 0.6 0.2 | ||||||
16 | Opening speed | m/s | 1.0 0.2 | ||||||
17 | Contact bouncing duration at closing operation | ms | 2 | ||||||
18 | Simultaneity of three phase closing operation | ms | 2 | ||||||
19 | Closing time | ms | 75 | ||||||
20 | Opening time | ms | 65 | ||||||
21 | Driven Power voltage of Permanent magnetic mechanism
| V | DC220 | ||||||
22 | Storage life | S | <10 | ||||||
23 | Control voltage of closing | V | 110220 | ||||||
24 | Control voltage of opening | V | 110220 | ||||||
25 | Main circuit resistance |
| 45 | ||||||
26 | Distance between phases | mm | 210,275(40kA) |