Welcome to B2BAGE
LG MCCB
LG MCCB

Minimum Order: 0
Quality/Safety Certification: 0.00


LG MCCB,CE marked ,3P,lower price,high quality,good service.

 

ABS&ABE MOULDED CASE CIRCUIT BREAKER(MCCB)

1.       Application

     ABS&ABE series molded case circuit breaker ,MCCB is suitable for industrial or commercial power and lighting with AC 50/60Hz,rated working voltage up to AC 600V/DC250V,rated current up to 63A.Its a kind of economical breaker with the characters of stable and reliable function,beautiful appearance ,small size and long life.It can be used for conversion of line and infrequent starting motor.It can be attached to install the accessories which have protection function for avoiding loss-voltage,undervlotage.The product can install connection line with front board and back board,it also can equip hand-operating apparatus or motor-operating apparatus to control in a remote distance.

2.The rated insulation voltage for this series of circuit breaker is 690V,the rated operating voltage is 600Vmthe rated frequency is 50Hz,the other values for the main circuit.


 

Type

2 pole

ABS-32E

ABS-52E

ABS-52S

ABS-62E

ABS-62S

3pole

ABS-32S

ABS-53E

ABS-53S

ABS-63E

ABS-63S

30

50

60

5,10,15,20,30

5,10,15,20,30,40,50

60

600

600

600

600

600

690

690

690

900

900

6

6

6

6

6

Uitimate breaking

capacity

(KA,lucAC50/60Hz)

220V/240V

10

10

25

10

25

380V

7.5/5

7.5/5

14/10

7.5/5

14/10

415V

7.5/5

7.5/5

14/10

7.5/5

14/10

440/460V

5

5

10

5

10

480/500V

2.5

2.5

7.5

2.5

7.5

600V

2.5

2.5

5

2.5

5

Utilisation category

A

A

A

A

A

Endurance

Mechnical

8500

8500

8500

8500

8500

Electrical

1500

1500

1500

1500

1500


 

Type

2 pole

ABE-102E

ABE-102S

ABE-203E

ABE-203S

ABE-403E

ABE-403S

3 pole

ABE-103E

ABE-103E

Frame size (AF)

100

225

400

Rated current(A)

5,10,15,20,30,40,50,60,75,100

15,20,30,40,50,60,75,100

100,125,150,175,200,225

250,300,350,400

Rated operational voltage(V)Ue(50/60Hz)

600

600

600

600

600

600

Rated insulation voltage (v)Ui(50/60Hz)

690

690

690

690

690

690

Rated impulse withstand voltage(KV)Uimp

6

6

6

6

6

6

Uitimate   breaking

capacity

(KA,lcu AC 50/60Hz)

220/240V

10

10

35

50

35

50

380V

7.5/5

7.5/5

18

25

30

42

415v

7.5/5

7.5/5

18

25

25

35

440/460V

5

5

18

25

25

35

480/500V

2.5

2.5

7.5

10

18

25

600V

2.5

2.5

7.5

10

18

22

Utillisation   category

A

A

A

A

A

A

Endurnce

Mechanical

8500

8500

7000

7000

4000

4000

Electrical

1500

1500

1000

1000

1000

1000