Vacuum Circuit Breaker
Vacuum Circuit Breaker

Minimum Order: 0
Quality/Safety Certification: 0.00


ZW6-12/630-16(20) Outdoor Vacuum circuit breaker

ZW6-21/630-1620type outdoor vacuum circuit breaker accounts for three-phase electrical system with 12 KV and 50Hz, mainly used in network for breaking or closing load current, overload current and short-circuit current, or used as breaking switch in ciry 12kV degree network.

Table 1 for installing parameter
NumberItemUnitPrameter
1Contact distance mm9±1
2Contact travel3±1
3Average switch-on speedm/s0.6±0.2
4Average switch-off speed1.0±0.2
5Contact switch-on bounce time ms≤2
6Three-phase switch-off conespnding time ms≤2
7Switch-on time s≤0.1
8Switch-off timeMax.Operating voltage D≤0.06
Min.Operating voltage ≤0.1
9Each phase loop DC resistance μΩ≤200
10Distance between phases (arc room) mm193
Table2 for rated technique parameter
NumberItemUnitPrameter
1Rated voltageKV12
2Rated insulating level 1min power DryKV42
Wet(to ground)34
Lighting impulse voltage withstand (peak)75
3Rated currentA630
4Rated frequency Hz50
5Rated short circuit breaking current KA12.5,16,20
6Rated short circuit closing curent (peak)31.5,40,50
7Rated short circuit closing current 31.5,40,50
8Rated short-times of rated short-circuit 4S12.5,16,20
9Operating order off-0.3S-on-off-180S-on-off
10Breaking times of rated short-circuit 30
11Mechanical life 10000
12Rated operating voltage with CT spring operating dvice VDC24,48V AC DC110V,220V
13Permitted grinding thickness of contact mm3
14Rated current of over-current tripA5
15Weightkg130(standard)