according to IEC60898-2 and GB10963.2 standards,used in circuit breaker with voltage of 250V,500V,750V,1000V and rated current
1. Application
The DC mini circuit breaker are produced according to IEC60898-2 and GB10963.2 standards,used in circuit breaker with voltage of 250V,500V,750V,1000V and rated current of 1~100A for overload and short-circuit protection, common used at DC power,electric locomotive,metro,ship and power supply.
2. Specification
The circuit breaker have performance of small volome,high breaking capacity,short arcing distance,fast close and convenient installation.
Special permanent magnetic field arc blow technology can ensure the reliability and stability of DC arc breaking.
Special designed arc leading part can lead the arc to arc chamber and help the permanent magnetic lead the arc to arc fence fastly.
The circuit breaker can used with various kinds of accessories (OF,SD,MX+OF,MN etc.)
The circuit breaker can assembled to multi poles (2,3,4 poles) according to different voltage and breaking capacity to satisfy customer’s requirement.
The circuit breark can be special designed according to customer’s special requirement.
3. Technical data
Pole | 1P | 2P | 3P | 4P |
Rated voltage Ue | 250V DC | 500V DC | 750V DC | 1000V DC |
Rated current In | B curve:6A,10A,16A,20A,25A,32A, | |||
C curve:1A,2A,3A,4A,6A,10A,16A,20A,25A, | ||||
Rated short circuit breaking capacty Icn(T=4ms) | 1P(125V):10kA,2P(250V:10kA,3P,4P(440V):6kA | |||
Instantaneous tripping type | B curve(4~7In),C curve(7~15In) | |||
Delay tripping time | cold state 1.13In | |||
hot state 1.45In | ||||
Rated withstanding voltage Uimp | 4kV | |||
Mechinal life | 10000 times | |||
Enviorment | Ambient temperature:-5°C~+40°C | |||
Applicable auxiliary parts | OF auxiliary contact,SD alarming contact, | |||
Max wiring capacity | 25mm2~50mm2 | |||
Standards | IEC60898-2 GB10963.2 |
4. Wiring diagram
5. Wiring conduct area parameter
Rated current(A) | Conduct area |
6A and below | 1mm2 |
10A | 1.5 mm2 |
16A,20A | 2.5 mm2 |
25A | 4 mm2 |
32A | 6 mm2 |
40A,50A | 10 mm2 |
63A | 16 mm2 |
80A | 25 mm2 |
100A | 35 mm2 |
6. Figure and installation dimension.
9. Din rail dimension.