Welcome to B2BAGE
ZW32-12(G) outdoor high voltage vacuum circuit breaker
ZW32-12(G) outdoor high voltage vacuum circuit breaker

Minimum Order: 0
Quality/Safety Certification: 0.00


1.vacuum circuit breaker with IEC standard
2.Rated voltage 12KV
3.Rated current 400/630
4.Rated short-circuit breaking curre

ZW32-12(G) outdoor high voltage vacuum circuit breaker

ZW32-12(G) type outdoor high voltage vacuum circuit breaker is appropriate to 50Hz three phase alternating current system, applicable for power grid breaking, loading current, overload current and circuit breaking current closing in power system. They can be used as segment switch in urban 12kv power grid, also assemble disconnecting switch according to customer’s requirement to be a assembled circuit breaker.

 

Ambient condition

1 Ambient temperature: max +40°C min –40°C

2 Altitude: ≤2000m

3.Wind pressure: ≤700Pa(equals to wind speed 34m/s)

3 Relative humidity: daily average relative humidity: ≤95%; monthly average relative humidity≤90%

4 Air contamination degree: III degree, far away from corrosive and combustible gas

5 Max daily temperature variation: ≤25°C

6 Earthquake intensity: ≤8 degree

7 The installation should be free from fire, explosion, severe vibration, chemical corrosion and serious pollution

.

Order instruction

Complete model and order quantity of the product

Rated current, rated voltage, rated breaking current, operation voltage

Transform ratio of assembled current mutual inductor

 

Main Technical Data    
Rated voltage                                                             kv12
Rated frequency                                                         Hz50
Rated lighting impulse withstand voltagekvInterphase or to ground 75,fructure 80
Rated short-time power frequency withstand voltage    kvInterphase or to ground 42,fructure 48
Rated current                                                             A400630630
Rated short-circuit breaking current                              kA12.51620
Rated short-circuit making current                               kA31.54050
Rated short-time withstand current                         kA12.51620
Rated peak withstand current                               kA31.54050
Rated operations of short-circuit breaking current interruption   times30
Rated operating sequence                                             0-0.3-CO-180s -CO(electric mechanism)
Mechanical life                                           times10000
Contact erosion limit                                       m3
Rated operating voltage of opening and closing coil                                        v         AC,DC220       AC,DC110         
Rated working current of overcurrent and tripping coil A5
Current transformer current ratio of two times(normal)  200/5,400/5,600/5
Rated voltage of energy saving motorv  AC,DC220       AC,DC110
Power of energy saving motorw≤200
Closing time ms20~40
Opening time ms30~60
Weightkg85

Mechanical characteristics adjustment data

Rated contact stroke                                  9±1mm

Contact overtravel                                     2±0.5mm

Average opening speed                             1.2±0.3m/s

Average closing speed                               0.6±0.2m/s

Contact bouncing duration at closing operation ≤2ms

Three-pole simultaneity                             ≤2ms

Condactive circuit resistance of each phases <80μΩ