Welcome to B2BAGE
VS1 Series Indoor High Voltage Vacuum Circuit Breaker
VS1 Series Indoor High Voltage Vacuum Circuit Breaker

Minimum Order: 0
Quality/Safety Certification: 0.00


1. It is for three-phase AC 50Hz.
2. It fits the IEC standard.

In General

VS1 Series Indoor HV Vacuum Circuit Breaker is the indoor HV switch with three-phase AC 50Hz, rated 7.2-12kV voltage. This circuit breaker fits the GB1984<AC HV breaker>, Jb3855<3.6~40.5kV indoor vacuum circuit breaker>, DI403<10-35kV indoor HV vacuum circuit breaker order technical specifications>and IEC standard, and possesses the reliable interlock merit ability. The breaker can carry on operation frequently, possesses the ability of opening or breaking many times and quick coinciding the floodgate. The breaker is designed front and back branch load structure, and can regard the cell installed fixed admittedly, but also can pretend to be the handcart use with hand car.

 

Type designation

V   S   1—12 / ◊-Ο                   

                                  Ο:  Rated short-circuit breaking current (kA)

                                  ◊ : Rated current (A)

                                 12: Rated voltage (kV)

                                  1:  Design item number

                                  S: Senyuan design

                                  V:  Vacuum circuit breaker

 

Main technical data

Rated voltage (kV)

12kV

Rated frequency

50Hz

Rated lighting impulse trial voltage/Fracture

75/85kV (peak value)

Rated 1 min power frequency withstand voltage/ Fracture

42/48kV (r.m.s)

Rated operative sequence

O-t-CO-t’-CO

 

 

Circuit breaker model

Rated current(A)

Rated short-circuit breaking current(kA)

Rated short-circuit making current (peak value) (kA)

Rated short-circuit keeping time(S)

Breaking times

Mechanical endurance

VS1-12/…

630

1250

20/25

50/63

4

100

20000

1250

1600

2000

2500

31.5

80

4

50

20000

1250

1600

2000

3150

40

100

4

30

10000

Note: 20kA    25kA     31.5kA     t=0.3s     t’=180s

           40kA                                   t=180s     t’=180s

 

Overall structure

 

VS1 Series Indoor HV Vacuum Circuit Breaker architectural structure uses operation organization and front and back load extinguish arc room, the leading electricity loop feature is three-phase console model constructs. The arc room vertical installs in pope type insulation muff, the insulation muff is poured by APG’s technology, thus it especially resisted creeping discharge. This kind of design has reduced the dust greatly together on the surface of arc room, and not only can prevent the vacuum arc room from influence of outside, but also can ensure to appear high prevent type even in the environment of damp and hot and serious filth environment.

 

 

 

Ads by Google



About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.