Welcome to B2BAGE
RICARDO Diesel Generator(24KW-150KW)
RICARDO Diesel Generator(24KW-150KW)

Minimum Order: 0
Quality/Safety Certification: 0.00


1)RICARDO Diesel Generator(24KW-150KW)
2)electricity(A) 43.2-270
3)frequency(HZ) 50/60
4) 3-phase, four-write
5)water-cooled

  RICARDO Diesel Generator(24KW-150KW) Technical Specifications:

Model

RICARDO DIESEL GENERATOR

Rated Power(KW)

24KW-150KW

Power factor

0.8

Rated voltage(V)

400/230

Rated electricity(A)

43.2-270

Rated frequency(HZ)

50/60

Output mode

Three-phase,four-write

Model

R495 K4100 R4105 R6105 R6113

Starting method

Electric

Cooling method

Forced water cooling

Lubrication

Coppound type with pressure and splash 

Crankshaft Ratating Direction

Ounter clockwise( Facing to the power out put end)

 

 

 

 

 

 

 

 

 

 

 

 

1) Output range:  Output range: 24KW-150KW

2) Engine details: Ricardo series

3) Alternator details: Stamford series, Marathon series, Lerysomer series, and so on.

4) Water-cooled

5) 8hrs operation base tank

6) Key start / auto start

7) Sound-proof / weather-proof canopy is optional

8) 230 / 400V  AC, 50Hz / 60Hz, 0.8pF three-phase and four wires alternating current output

9) Frequency: <3%

10) Frequency at stable state: <0.5%

11) Frequency deviation at instantaneous state: ≤+10%

12) Frequency return time: ≤3s

13) Voltage deviation at stable state: ≤±1%

14) Voltage deviation at instantaneous state: ≤+20%

15) Voltage return time: ≤4s

16) Voltage modulation: ≤0.3%

17) Standard configuration of gensets: a) Engine: R series diesel engine

b) Engine type: water-cooled, in line four-stoke, direct injection c) Alternator: Marathon brushless alternator

18) Control system: a) Automatic alarm system: the unit has the acoustic-optics

alarm system and arrestor for any situation as the start defeat, the water is

over temperature, the oil pulls down, over speed, over load and over current b)

Operation display: i) Unit voltage, tri-phase load current and frequency display

ii) Water temperature, oil pressure display iii) Fuel level, fuel temperature

display iv) Audible and visual alarm lamps and buzzers

19) Starting system: DC alternator is used to start engine

20) Short circuit protection: MCCB air switch

21) Cooling system: combined cooling water tank fitted to meet the requirement

of radiation at ambient temperature 40°C

22) Filter system: oil, fuel and air filter

23) Accessories: exhaust elbow, bellow, muffler

24) Supply standard collocation:

a) Diesel engine with all accessories, 3 filter, electric systems

b) Alternator

c) Steel structure

d) Fan and water tank cooling system

e) Flange connector

f) 12 / 24V starting motor and charge engine

g) Air cleaner, fuel cleaner, oil cleaner

h) On-board control panel

i) MCCB air conservation switch

j) 12 / 24V starting accumulator and Battery line

k) Set shock absorber

l) High-efficient silencerInner

25)packing: packing in Wooden cases

 

 

 

 

 

 

 