BV 300/500 electrical wire long term working temperature70oC
NO. | Nominal Section(mm2) | Number/Diameter of core(mm) | Nominal Outer Diameter(mm) | Max. Outer Diameter(mm) | Weight(kg/km) | Conductor Resistance at 20(≤Ω/km | Insulated Resistance at 70(≤KΩ/km |
1 | 0.5 | 1/0.80 | 2.0 | 2.4 | 8 | 36 | 0.015 |
2 | 0.75 | 1/0.97 | 2.17 | 2.6 | 10 | 24.5 | 0.012 |
3 | 0.75 | 7/0.37 | 2.31 | 2.6 | 11 | 24.5 | 0.014 |
4 | 1.0 | 1/1.13 | 2.33 | 2.8 | 13 | 18.1 | 0.011 |
5 | 1.0 | 7/0.43 | 2.49 | 2.8 | 14 | 18.1 | 0.013 |
227IEC01(BV)electrical wire long term working temperature70oC
NO. | Nominal Section(mm2) | Number/Diameter of core(mm) | Nominal Outer Diameter(mm) | Max. Outer Diameter(mm) | Weight(kg/km) | Conductor Resistance at 20(≤Ω/km | Insulated Resistance at 70(≤KΩ/km |
1 | 1.5 | 1/0.38 | 2.78 | 3.3 | 19 | 12.1 | 0.011 |
2 | 1.5 | 7/0.52 | 2.96 | 3.4 | 20 | 12.1 | 0.01 |
3 | 2.5 | 1/1.78 | 3.38 | 3.9 | 30 | 7.41 | 0.01 |
4 | 2.5 | 7/0.68 | 3.64 | 4.2 | 33 | 7.41 | 0.009 |
5 | 4 | 1/2.25 | 3.85 | 4.4 | 45 | 4.61 | 0.0085 |
6 | 4 | 7/0.85 | 4.15 | 4.8 | 48 | 4.61 | 0.0077 |
7 | 6 | 1/2.76 | 4.36 | 4.9 | 64 | 3.08 | 0.007 |
8 | 6 | 7/1.04 | 4.72 | 5.4 | 68 | 3.08 | 0.0065 |
9 | 10 | 1/3.57 | 5.57 | 6.4 | 111 | 1.83 | 0.007 |
10 | 10 | 7/1.35 | 6.05 | 6.8 | 173 | 1.83 | 0.0065 |
11 | 16 | 7/1.70 | 7.10 | 8 | 169 | 1.15 | 0.005 |
12 | 25 | 7/2.14 | 8.82 | 9.8 | 271 | 0.727 | 0.005 |
13 | 35 | 7/2.52 | 9.96 | 11 | 367 | 0.524 | 0.004 |
14 | 50 | 19/1.78 | 11.70 | 13 | 480 | 0.387 | 0.0045 |
15 | 70 | 19/2.14 | 13.50 | 15 | 676 | 0.268 | 0.0035 |