1,automatic
2, fire extinguisher
AW-GEC2158 Automatic fire extinguisher control panel
ITEM | ELECTRICAL RATING | COMMENT |
Mains supply | 90 to 270VAC, 50Hz/60Hz(100 Watts maximum) |
|
Mains supply fuse | 3 Amp ( F3A L250V) | Replace only with similar type |
Power supply rating | 3 Amps total including battery charge 28V +/- 2V |
|
Maximum ripple current | 200 millivolts |
|
Battery type | Two 12 Volt sealed lead acid in series. | 7Ah maximum |
Battery charge voltage | 27.6VDC nominal |
|
Battery charge current | 0.7A maximum |
|
Battery fuse | 20mm, 3.15 glass |
|
Current draw in mains fail condition | 0.095 Amps | With buzzer sounding |
Current draw in second stage alarm | 0.235A | Two zones in fire(470 ohm in circuit) |
Current draw in post discharge condition | 0.310A | solenoid outputs active |
Maximum current draw from batteries | 3Amps | With main power disconnected |
R0V output | Fused at 500Ma with electronic fuse |
|
Sounder outputs | 21 to 28V DC Fused at 500mA with electronic fuse | 1.6Amp total load over all circuits |
Fault relay contact rating | 5 to 30VDC 1A Amp maximum for each | Volt free changeover contact |
Fire relay contact rating | 5 to 30VDC 1A Amp maximum for each | Volt free changeover contact |
Local fire relay contact rating | 5 to 30VDC 1A Amp maximum for each | Volt free changeover contact |
First stage contact rating | 5 to 30VDC 1A Amp maximum for each | Volt free changeover contact |
Second stage contact rating | 5 to 30VDC 1A Amp maximum for each | Volt free changeover contact |
Extract contact rating | 5 to 30VDC 1A Amp maximum for each | Volt free changeover contact |
Zone quiescent current | 0mA minimum, 2mA maximum |
|
Terminal capacity | 0.5mm2 to 2.5mm2 solid or stranded wire |
|
Number of detectors per zone | Dependent on type |
|
Number of sounders per circuit | Dependent on type and current consumption |
|
Detection circuit end of line | 6K8±5% 1/2 Watt resistor |
|
Monitored input end of line | 6K8±5% 1/2 Watt resistor |
|
Sounder circuit end of line | 10K±5% 1/2 Watt resistor |
|
Extinguishant output end of line | 1N4004 Diode |
|
No. of detection circuits | Four 21 to 28V DC |
|
No. of sounder circuits | Three 21 to 28V DC | 2X first stage, 1 X second stage |
Extinguishant release output | 21V to 28V DC. Maximum load 1 Amp |
|
Extinguishant release delay | Adjustable 0 to 75 seconds | 5 second steps |
SIL, AL, FLT, RST inputs | Switched –ve, min resistance 0 ohms, max 470 ohms |
|
Zone normal threshold (Allowable EOL) | 10K ohms to 2K ohms | Use 6K8 end of line resistor |
Detector alarm threshold | 1K ohms to 390 ohms |
|
Call point alarm threshold | 370 ohms to 150 ohms |
|
Short circuit threshold | 130 ohms to 0 ohms |
|
Head removal condition | 15.5 to 17.5 volts+/- 5% |
|
Cabling | FP200 or equivalent | Metal cable glands must be used. |
Monitored inputs normal threshold | 10K ohms to 2K ohms |
|
(Allowable EOL) | ||
Monitored inputs alarm threshold | 2K ohms to 150 ohms+/-5% |
|
Monitored inputs Short circuit threshold | 140 ohms to 0 ohms+/-5% |
|
Status unit/Ancillary board connection | Two wire RS485 connection with electronic fuse. | Max. of 16 units-RS485 data cable |
Status unit power output | 21 to 28V DC, Fused at 500mA with electronic fuse. | 300 milliamp maximum load |