1.Operating VoltageAC220V(+5%,-15%),50Hz
2.Storage Batteries: The capacity of the batteries is supplied according to panel type and user's damand.The maximum capacity is 7Ah(for L8,L16)
3.Output Parameters:
1)Detector operating Voltage:DC20-24V
2) Standby Current:2.5mA(when connected with 25 conventional detecctors)
3)Terminal Resistor10k ohm
4) Sounder output Voltage:DC20-24V
5) Sounder output current:1A
6) Sounder Terminal Resistor10k ohm
7)Fire output:AUX,power output:1A,DC24V
8) Fault output:AUX,power output:1A,DC24V
4. Unit Dimension: 320x230x90(mm)

5. 8zone,16zone---optional