Welcome to B2BAGE
High-performance Intelligent Flow-integrating Instrument
High-performance Intelligent Flow-integrating Instrument

Minimum Order: 0
Quality/Safety Certification: 0.00


High-performance Intelligent Flow-integrating Instrument
- mass, volume or length
-batch control
-CE,CQC,ISO9001

 

 

AI-808H Mass Flow Meter

High-performance Intelligent Flow-integrating Instrument

 

Main Features

- Modularized structure compatible with AI series instruments and modulesModularized and configurable inputs. - 1-5V, 0-5V, 4-20mA, Pt100 RTD, K, E, J type thermocouple, voltage, or current signal- Functions:retransmission, high/low alarm of momentary flow, temperature and pressure,  abnormal signal detecting, and communication- Square root/no square root selectable-8-digits accumulation value and 4-digits momentary process value- batch controller, 4-bit accumulator ,12-bit accumulator for total sum individually.
- 14 bit output resolution -0.2%FS output precision.

 

Specification:

Control mode

On-off control mode (deadband adjustable)
AI MPT with auto tuning, adopting fuzzy logic PID algorithm.

Measurement

accuracy

0.2%FS ± 0.1°C

Resolution

0.1°C (automatically change to 1°C when the temperature is high than 999.9°C) or 1°C

 selectable

Temperature drift

≤0.01%FS /°C (typical value is 50ppm/°C)

Response time

≤0.3s ( when digital filter parameter dL=0)

Input

Thermocouple: K, S, R, T, E, J, N, WRe3-WRe25, WRe5-WRe26

Resistance temperature detector: Cu50, Pt100

Linear voltage: 0~5V, 1~5V, 0~1V, 0~100mV, 0~60mV, 0~20mV, etc.;

 0~10V if module I31 is installed on MIO socket.

Linear current (external connect to precise shunt resist

 or install I4 module on MIO): 0~20mA, 4~20mA, etc.

Linear resistance : 0~80ohm, 0~400ohm.

Optional: apart from the above-mentioned Input type, an additional type can

 be provided upon request.(Graduation index is needed)

Input range

Thermocouple: K(-100~1300°C), S(0~1700°C), R(0~1700°C),

 T(-200~+390°C), E(0~1000°C), J(0~1200°C),B(600~1800°C),

 N(0~1300°C), WRe3-WRe25(0~2300°C), WRe5-WRe26(0~2300°C)

Resistance temperature detector:Cu50(-50~+150°C), Pt100(-200~+800°C)

Linear Input: -9990~30000 defined by user.

Output

(modularized)

Relay output (NO+NC): 250VAC/2A or 30VDC/1A

TRIAC no contact discrete output (NO or NC): 100 ~240VAC/0.2A (continuous),

 2A (20mS instantaneous, repeat period≥5s)

SSR Voltage output: 12VDC/30mA (used to drive SSR)

Thyristor zero crossing trigger output: can trigger TRIAC of 5~500A, 

a pair of inverse paralleled SCRs or SCR power module

Linear current output: 0~20mA, 4~20mA (The output voltage of X module ≥10.5V; 

and that of X3 module ≥10.5V.)

General specifications

Voltage: support AC85-265V,50/60Hz or DC24V. 

Power consumption: ≤5W or ≤0.8W if no alarm and output

Isolation withstanding voltage :

between power, relay contact or signal terminal ≥2300VDC;

between isolated electroweak terminals ≥600VDC

Electromagnetic compatibility (EMC) : ±4KV/5KHz according to IEC61000-4-4; 

4KV according to IEC61000-4-5.

Operating Ambient : temperature -10~60°C; humidity ≤90%RH