1.DSE702 Auto Start Control Module
2.Accept OEM and Small and mix order
3.Best service all the time
4. Fast shipping

DSE702 Auto Start Control Module

The DSE702 is available in Manual and Auto Start versions, offering an excellent range of engine monitoring and protection features.

The module has been designed to monitor low oil pressure, high engine temperature, over speed and a user defined auxiliary input.

It also has the capability to monitor battery charging by utilising the WL terminal on the charge alternator. When themodule detects a fault condition it automatically shuts down the engine.

The DSE701 modules include a remote start signal input. This input allows the module to be started from a pre-defined remote location.

 

FEATURES

Manual start                                                             Engine pre-heat

Engine monitoring and protection features       Protected solid state (PSS) outputs

Front panel mounting                                            Tamper proof engine hours counter

Remote start                                                            LED indicators

 

 BENEFITS

Hours counter provides accurate information for monitoring maintenance and warranty periods;

Multiple engine parameters are monitored simultaneously

 

 MANUALMODE

The module is started using the on-board key/buttons

The user turns the key to the position

The engine pre-heat button is then pressed for the required time

The start button is then pressed to start the engine

To stop the engine the key needs

 

AUTOMATICMODE

The key needs to be permanently left in the position

The module is powered up by the remote start signal

The pre-heat function is automatically carried out and then the engine is started

To stop the engine the remote switch is turned to the off position

 

OVERSPEED PROTECTION

The engine over speed trip setting can be calibrated at the rear of the module for 50Hz or 60Hz nominal operation (57Hz or 68Hz trip respectively).

During engine cranking and for the first 10 seconds after the engine starts running, all alarm conditions are suspended (overspeed is enabled) to allow the engine to reach its optimum running speed.

 