high temperature heat pump
Minimum Order: 0
Quality/Safety Certification: 0.00
With special materials and technics,the unit's outlet hot water temperature can reach 80C,which can meet industrial customers.
With special materials and technics, the unit's outlet hot water temperature can reach 80°C,which can meet the special requirements of industrial customers. Circulation type or Direct-heat type is for optional according to different customer's requirement. It is used in wood, leather, fabric, and grain drying and begin to be popular because of energy saving for these industrial customers.
Parameters for Air Source Heat Pump | |||||||||
Model | KRS-09/AB | KRS-15/AB | KRS-19/AB | KRS-24/AB | KRS-40/AB | KRS-60/AB | KRS-75/AB | KRS-90/AB | |
Heating Capacity(KW) | 9.00 | 15.00 | 19.00 | 24.00 | 40.00 | 60.00 | 75.00 | 90.00 | |
Rated Input power(KW) | 2.14 | 3.57 | 4.52 | 5.71 | 10.00 | 14.80 | 18.70 | 22.50 | |
Max Input power(KW) | 2.65 | 4.60 | 5.80 | 7.40 | 13.30 | 19.00 | 24.50 | 29.00 | |
Rated Input current(A) | 3.30 | 9.00 | 7.60 | 10.50 | 15.00 | 21.00 | 27.70 | 31.00 | |
Max Inputcurrent(A) | 3.60 | 9.50 | 9.80 | 13.50 | 19.00 | 26.00 | 36.00 | 34.50 | |
Voltage(V) | 380.00 | ||||||||
COP | 4.20 | 4.00 | |||||||
Highest output water temperature(°C) | 60 | ||||||||
Rated output water temperature(°C) | 55 | ||||||||
Rated working water pressure(Mpa) | 0.70 | ||||||||
Circulation pump water flow(M3/h) | 1.50 | 2.40 | 3.20 | 3.70 | 5.50 | 9.50 | 13.00 | 15.50 | |
Net Dimension | Length(mm) | 700.00 | 930.00 | 810.00 | 1450.00 | 1450.00 | 1900.00 | 2000.00 | 2200.00 |
Width(mm) | 700.00 | 390.00 | 780.00 | 780.00 | 780.00 | 1010.00 | 1030.00 | 1030.00 | |
Height(mm) | 900.00 | 1270.00 | 1050.00 | 1050.00 | 1050.00 | 1250.00 | 2090.00 | 2090.00 | |
Water pipe connector | G1" | G2" | |||||||
Working ambient temperature(°C) | (-)7~43 | ||||||||
Weight(Kg) | 105.00 | 105.00 | 112.00 | 215.00 | 268.00 | 475.00 | 585.00 | 690.00 | |
Operation Noise(dBA) | ≤55dB(A) | ≤55dB(A) | ≤60dB(A) | ≤65dB(A) | ≤65dB(A) | ≤68dB(A) | ≤70dB(A) | ≤70dB(A) | |
Type of waterproof | IPX4 | ||||||||
Type of electrical shock protection | I | ||||||||
Note:The above mentioned data are tested by the ambient temperature:DB:20°C,WB:15°C,Inlet water temperature 15 °C,Outlet water temperature 55°C |