Ground source heat pump
380V/50HZ
for commercial use

CWM series Ground source heat pump can connect to indoor fan coils, for cooling in summer and heating in winter, any supply hot water for whole year! It is specailly energy saving as in summer, while do cooling, hot water is provided for free of charge!

 

This Clitech water source heat pump CWM is applicable for different installation conditions of deep underground water system, shallow ground water system and water pipe laying in soil system.

System introduction:  

1 Scroll compressor inside.  

2 Compact structure, easy demountable for access.  

3 Environment friendly refrigerant of R410A or R417A is available.  

4 Intelligent controller adjustment by quickmind microprocessor.  

5 Four way directional valve.  

6 Careful protections like high/low pressure protection, water flow switch protection, overheating protection, overload protection and so on.  

7 Fault self-checking function

Technical Parameters:

Air-conditioner and water heater integrated unit (water  source)

Model

unit

CWM-40

Sanitary hot water working condition

Rated heating capacity

kw /BTU

35 /118400

hot water supply

T/h

0.75

Heating input power

kw

7.43

rated input current

A

14.86

COP

 

4.7

Heating  for AC

heating capacity

kw /BTU

27.1 /92500

heating input power

kw

5.8

heating input current

A

11.6

EER

 

4.67

Cooling for AC

cooling capacity

kw /BTU

23.9 /81570

cooling input/consumed power

kw

6.3

cooling input current

A

12.8

COP

 

3.79

AC cooling with water heater

average cooling capacity

kw /BTU

23.5 /80200

Average heating capacity

kw /BTU

30 /102400

Hot water supply

T/h

0.6

Average input/consumed power

kw

6.1

Average input current

A

12.2

COP+EER

 

8.8

Power source

V/Ph/Hz

380V-415V/50Hz

 Rated and the max outlet water temp.

°C

55°C  and 60 °C

Noise

Db(A)

58

Dimension

Width

mm

800

Depth

mm

1080

Height

mm

1300

Weight

kg

260

Throttle type

 

The equilibrium thermal expansion valves

Refrigeration

Type

 

R417A/ R407C/R410A optional

 Charge

kg

4

Compressor

Type

 

Scroll

Rated test conditions:

1:Hot water conditon:water source side inlet water temp is 15°C, initial hot water temp is 15°C and ending temp is 55°C.
2. Cooling working condition: water source side inlet water temp is 18°C, outlet temp is 29°C, user-side inlet water temp is 12°C, outlet temp is 7°C.

3. Heating working condition: water source side inlet water temp is 15°C, user-sider inlet water temp is 40°C, water flow the same to summer water flow.

4. Cooling and hot water working condition: initial hot water temp is 15°C, ending temp is 55°C; Air conditoner side water inlet temp is 12°C, and outlet temp is 7°C.

Related Products
Ads by Google



About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.