H2, 3 and 4 humidity and temperature transmitters are HAVC sensors
Applications
H2, 3 and 4 humidity and temperature transmitters are designed for environment monitoring and controlling in industrial and commercial buildings. These transmitters can be used for:
Humidity and temperature monitoring of supply, exhaust and return air (H2, duct mount)
Humidity and temperature monitoring in critical environment such as outside air (H3, outside mount)
Other applications of immersion humidity and temperature monitoring (H4, separate probe)
Features
High performance digital sensors and circuits, ensure accurate measurement and temperature compensation
Good long term stability and reliability
100% field changeable sensors, no re-calibration needed
Fast response
Multiple output signals selectable
Industrial design, SS probe and selectable filter
High protection rate up to IP65
Applications
H2, 3 and 4 humidity and temperature transmitters are designed for environment monitoring and controlling in industrial and commercial buildings. These transmitters can be used for:
Humidity and temperature monitoring of supply, exhaust and return air (H2, duct mount)
Humidity and temperature monitoring in critical environment such as outside air (H3, outside mount)
Other applications of immersion humidity and temperature monitoring (H4, separate probe)
Features
High performance digital sensors and circuits, ensure accurate measurement and temperature compensation
Good long term stability and reliability
100% field changeable sensors, no re-calibration needed
Fast response
Multiple output signals selectable
Industrial design, SS probe and selectable filter
High protection rate up to IP65
Specifications
Relative Humidity:
Sensor: Capacitance polymer
Range: 0~100%RH
Output: 4~20mA /0~10VDC/RS485
Accuracy: 2%, 3% and 4.5%RH(25°C, 20~80%RH)
Hysteresis: <±1%RH
Response time: <10s (25°C, in slowly flow air)
Drift: <±0.5%RH/year
Temperature:
Sensor: Solid state band gap, RTD or thermistors
Range: 0~50°C for transmitter
Output: 4~20mA/0~10V/RS485, RTD or thermistors
Accuracy: see model table
Power: Voltage 15~35VAC/DC, Current 7.5-36VDC
Output Load: <500Ω (current),
>2KΩ (voltage)
Temperature Limit: -40~85°C,
0~95%RH (Non condensing)
Storage Temperature: -40~80°C
Housing: ABS Enclosure, SS probe, SS sintered or mesh filter
Protection: IP65
Accessory: install flange
Optional MMI operation panel: Including LCD, integrated with function keys, can be ordered and operated in field separately(H2/3/4). See details on MMI product.
Models:
TO BE SUPPLYED