Neutrality point outdoor high voltage AC disconnector 40.5/72.5/126kV
Minimum Order: 0
Quality/Safety Certification: 0.00
Outdoor high voltage AC diconnector.
dirtiness resistance
outdoor disconnectors
Technical data:
GW13-40.5 72.5 126(W) Outdoor high voltage AC disconnector | ||||
Item | Unit | Value | ||
Rated voltage | kV | 40.5 72.5 126 | ||
Rated insultaing level | 1min power frequency withstand volatge(validvalue) | To the earth | kV | 95 160 230 |
Interrupter | kV | 118 200 230+70 | ||
Rated thunder impulse withstand voltage(peak) | To the earth | kV | 185 350 550 | |
Interrupter | kV | 215 410 550+100 | ||
Rated frenquency | Hz | 50 | ||
Rated current | A | 630 | ||
Rated short time withstand current | KA | 20 | ||
Ration peak withstand current | KA | 50 | ||
Rated short-circuit duration Main/earthing blade | s | 4 | ||
Rated terminal mechanical load | Horizontal portrait | N | 1000 | |
Horizontal transverse | N | 750 | ||
Vertical force | N | 750 | ||
Creepage distance | mm | 1013 1256 1813 2284 3150 3906 | ||
Mechanical life | times | 10000 | ||
Electromotor operating mechanism | Type | CJ6B | ||
Motor voltage | V | AC380 DC220 AC220 DC110 | ||
Control loop voltage | V | AC380 DC220 AC220 DC110 | ||
Manual operating mechanism | Type | CS17 CS17G | ||
Electromagnetic lock voltage | V | DC220 AC220 | ||
Weight of product | Single earthing | kg | 130 180 220 |
Outline dimension:
Order notice:
Type and specification of the outdoor disconnector
Working environment(ambient temperature, altitude, dirtiness level)
Type of operating mechanism
Name and quantity of the accessories and tools if required. (deal separated with disconnector)