CE certificate
Rated Output Power,1000KW
General Descriptions
SG1000KHV is the latest member of SUNGROW inverter family to provide a perfect turnkey solution for MW level PV powerstations. It consists of 2 units of high-efficient inverter(SG500KTL), one unit of medium-volt transformer (customized),AC&DC distribution boxes, monitoring and communication equipments. This advanced design not only facilitates the transportation and installation ,but also improves the system safety and reliability with increased efficiency and energy yield.
All the features above guarantee SG1000KHV the best choice for MW level PV power plants.
Technical Features
• Power reduction (100%, 60%, 30%, 0%) meet German EEG requirements
• Reactive Power Control with power factor from 0.9 lagging to 0.9 leading
• Megawatt PV power plant turnkey solution
• Optimized design for easy transportation and installation
• Non-polluted environmentally-friendly house
• Full protective functions and user-friendly monitoring interface
• With environment monitoring device
• Enhanced system efficiency by sharing one high-efficient isolating transformer with 2 inverters
• Auxiliary heater (optional)
• Max. working altitude at 6000m (operation with derating above 3000m)
• CE certification
Communications
• RS485/ Ethernet/ GPRS communication interfaces
• PC monitoring software
Safety
·Complete protective functions: over voltage
·short circuit, islanding,
·over heat, over load and lightning protection, etc.
·DC ground-fault protection
·Compliance with standards: EN61000-6-2,
·protection,
·EN61000-6-4,EN50178, RD1663/ 2000
Technical Specifications:
Modle | SG1000KHV |
DC SIDE DATA | |
Max. DC Voltage | 1000Vdc |
Start Voltage | 470V |
MPP Voltage Range | 450~820Vdc |
Min. DC Voltage | 450V |
Max. DC Power | 1100kWp |
Max. Input Current | 2400A |
AC SIDE DATA | |
Rated Output Power | 1000kW |
Rated Grid Voltage | 10/20/35KV |
Grid Voltage Range | - |
Rated Grid Frequency | 50Hz/60Hz |
Grid Frequency Range | 47~51.5Hz/57~61.5Hz |
Output Current THD | <3% (at nominal power) |
DC Current Injection | <0.5% of rated inverter output current |
Power Factor | 0.9(lagging)~0.9(leading) |
SYSTEM | |
Max. Efficiency | 97.8%(with transformer) / 98.7%(without transformer) |
Euro. Efficiency | 97.4%(with transformer) / 98.5%(without transformer) |
Protection Degree | IP54(outdoor) |
Power Consumption at Night | <1800W |
Operating Temperature | -25~+55°C |
Cooling Method | controlled forced-air cooling |
Relative Humidity | 0~95%, non-condensing |
Max. Working Altitude | 6000m (operation with derating above 3000m) |
DISPLAY AND COMMUNICATIONS | |
Display | touch screen LCD |
Standard Comm. Interfaces | RS485 |
Optional Comm. Interfaces | Ethernet/GPRS |
MECHANICAL DATA | |
Dimensions(WxHxD) | 10800x3150x2420mm |
Net Weight | 20t |