1.Clamp Size 80mm*80mm
2.Current Range 0.0mA~2000A
3.Current Resolution 0.1mA
4.Voltage Range 0.01V
Function Measure AC leakage current, current, there-phase, voltage
Test Mode Clamp CT, integral mode
Clamp Size 80mm×80mm
Current Range 0.0mA~2000A
Current Resolution 0.1mA
Voltage Range 0.00V~600V
Voltage Resolution 0.01V
Measurement Accuracy
(23°C±3°C, below 70%RH, measured wire at the center of the clamp) 0.00mA~300A: ±1.5%±3dgt
300A~1200A: ±2%±3dgt
1200A~2000A: ±3%±3dgt
0.00V~600V: ±1.5%±3dgt
Data Storage 200 Groups
RS232 Interface
Frequency 50Hz ,60Hz automatic identification
Gear Shift Automatic shift
Sample Rate About 2 times/second
Display Mode LCD: 128dots×64dots; Display area: 43mm×29mm
Meter Size Length 275mm × Width 145mm × Height 40mm
Backlight Controlled by LIGHT key
Data Hold “HOLD” symbol appears
Overflow “OL” symbol appears
Automatic Shutdown Automatically shutdown about 15 minutes after power on to reduce
Weight 1kg(with batteries and accessories)
Insulation strength AC 2kV/rms(between core and shell)
Safety Specifications IEC1010-1, IEC1010-2-032, 2 class of pollution
Power 6V DC(LR6×4 alkaline dry batteries, continuously working for 12 hours)