Low price and high reliability;
Temperature not-exceeding 120 Celsius degree at the centre and 90 Celsius degree at the ends.
Application
The interchangeable shunts are used to multiply the measuring ragne of current of measuring instruments.
Basic spcifications
1. Accuracy class:0.5 for 5-4000A and class 1 for 5000-15000A.
2.Ambient conditions:Temperature:-40°C ~+60°C relative humidity:95%(at35°C)
3.Capacity to wishstad mechanical force:lt is capable of withstanding the transport
bumping atacceleration of 70m/s2 and shock frequency of 80-120 times/mi for 6 hr.
4.Orerrating capacity:120% of rated current for 2hr.
5.Voltage drop:75mv
6.Giving out heat when loaded:not ge more than 80 after remperature rise gets
steady:not be more than 120°C at rated current of over 50A