Flame control with ionisation sensor
or UV sensor
Ignition and monitoring with a single
electrode
The automatic burner control units ignite and monitor gas burners in intermittent operation, i.e. the burners must be shut down once in every 24 hours. They are used in directly ignited gas burners of any capacity (ignition power ≤ 350 kW) in which, for technical reasons, pre-purging is omitted or controlled by a separate control system. Typical areas of application are industrial thermal process systems to EN 746 in the iron, steel, glass, ceramics, plastics processing and chemical industries. In addition, the IFS 258 are also suitable for use with atmospheric burners in other heatgenerating systems. The units are type-tested and certified in accordance with EC Directive 90/396/EEC for gas appliances in conjunction with EN 298.
Main modles as follow:
Model | IFS 258-3/1W | IFS 258-5/1W | IFS 258-10/1W |
Code | TC100001 | TC100002 | TC100003 |
Minimum switch-on time for the J signal: | 8s | 10s | 15s |
Mains voltage: | 230 V AC, -15/+10%, 50 Hz, for earthed and non-earthed systems. |
Power consumption: | Approx. 19 VA (7W).Output voltage for valve and ignition transformer = Mains voltage. |
Output current: | Max. 2 A per output, total current max. 2.5 A. |
Fuse in unit: | 3.15 A, slow-blow H, to IEC 127-2/5. |
Flame control: | Ionisation sensor or UV sensor. |
Sensor voltage or voltage at UV sensor: | Approx. 230 V AC. |
with UV control: | Max. 100 m |
Average number of operating cycles as a function of power factor cos j: | Approx. 1 x 106, with single-electrode operation:270000 |
Valve connections: | 1 |
Ambient temperature: | -20°C to +60°C, no moisture condensation admissible. |
Enclosure: | IP40 to IEC 529 |
in the area of the measuring sockets: | IP30 |
Construction: | Housing made of impact and heat-resistant plastic, plug-in upper section with operating controls and indicators.Bottom section (Fig. 15) with connection terminals, earth and pre-wired neutral bus with generous cable space. |
Weight: | 0.51kg |