generator AVR
this generator AVR
TECHNICAL SFECIFICATION
INPUT
Voltage 85-125 V ac
170-250 V ac Jump Selectable
Frequency 50-60 Hz nominal
Phase 1
OUTPUT
Voltage max 90 V dc at 207 V ac input
Current continuous 4A dc
Transient 6 A for 10 seconds
Field Resistance 15 ohm minimum
REGULATION (see Note 1) +/- 1%
THERMAL DRIFT (after 10 min)
1% for 40°C change in AVR ambient
TYPICAL SYSTEM RESPONSE Field current to 90% 80ms
Machine volts to 97% 300ms
EXTERNAL VOLTAGE ADJUSTMENT +/- 5% with 1 k ohm 1watt trimmer
UNDER FREQUENCY PROTECTION
Set point 95%Hz
Slop 170% down to 30Hz
UNIT POWER DISSIPATION
10 watts maximum
BUILD UP VOLTAGE
3.5V ac @ AVR terminals
ENVIRONMENT
Vibration 20-100Hz 50mm/sec
100Hz-2k Hz 3.3g
Relative Humidity 0-60°C 95%
Operating Temperature -40°C to +70°C
Storage Temperature -55°C to +80°C
DIMENSIONS
Outline Dimensions 104(W)×139(H)×39(D)(mm)
Installation Size 80(W)×115(H) (mm) ×Φ5-4
Color Black
Weight 300g