Welcome to B2BAGE
vacuum interrupter for load break switch
vacuum interrupter for load break switch

Minimum Order: 0
Quality/Safety Certification: 0.00


1.vacuum interrupter
2.Non-exposed arc
3.Once Seal-Exhaust
4.Oxygen-free copper ring transition in sealing structure

low and high voltage ceramic vacuum interrupter for load break switch
Main Technical Data  
Rated voltage                                            kv12
Rated current                                            A630
Rated frequency                                         Hz50
Rated short-time power frequency withstand voltage(1min)     kv42
Rated lighting impulse withstand voltage                     kv75
Rated short-time withstand current                         kA16/20
Rated withstand current(peak)                    kA40/50
Rated short-circuit making current kA40/50
Rated closed-loop breaking currentA630
Rated active load breaking current                A630
Rated cable charging breaking current                       A10
Rated single capacitor bank breaking currentrrent                               A400
Rated duration of short-circuit                              s4
Mechanical life                                           times10000
Contact closing force due to bellows and atmosphere          N70±40
Counterforce at rated contact stroke                          N120±50
Circuit resistance at rated contact force                      μΩ≤45
Shelf life                                                  years20
Contact erosion limit                                       mm3
Weight of moving parts                                                                             kg≤0.7
Mechanical Data Required For Matched Vacuum Switchgear                                             
Rated contact stroke                                      mm6±1
Average opening speed                                   m/s1.0±0.2
Average closing speed                                    m/s0.65±0.2
Added contact force                                       N700/900±50
Contact bouncing duration at closing operation                ms≤2
Contact bouncing bank amplitude of opening operation         ms≤2
Three-pole simultaneity                                     ms≤1
   
Note:Rated characteristics can be given on requirment  

Ads by Google



About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.