Combustible gas or CO
High-quality gas sensor and MCU control
Electrochemical sensor inside
CP01 gas detector, designed for car park use and commercial use, is suitable for detecting combustible gas and toxic gas like CO, H2S etc.
Detection principle: Electrochemical gas sensor or catalytic gas sensor
Range: 0-1000 PPM for CO?? 0-100% LEL for combustible gas
420mA signal output is compatible with all 420mA control systems
RS485 compatible
Protection degree: IP65
Working voltage: DC24V±25%
Relay output of high-alarm and low-alarm
Brief introduction
CP01 is a newly developed fixed gas detector of Hanwei. With high-quality electrochemical/catalytic gas sensor and excellent craftwork, it has the advantages of good repeatability, disturbing-proof against temperature and humidity, long life-span and easily operation.
It can transfer the gas concentration in air into digital signal output through 4-20mA electric current signal. It is suitable for gas detection in car parking or industrial environment where toxic gas or combustible gas leaks.
2. Technical Data
Model | CP01-A | CP01-B |
Working principle | Electrochemical (toxic gas) or Catalytic (combustible gas) | Electrochemical (toxic gas) or Catalytic (combustible gas) |
Detecting gas | CO or CH4 | CO or CH4 |
Detecting range | CO: 01000ppm or CH4: 0100%LEL | CO: 01000ppm or CH4: 0100%LEL |
Resolution | CO: 1ppm or CH4: 1%LEL | CO: 1ppm or CH4: 1%LEL |
Low alarm level | CO: 35ppm or CH4: 20%LEL | CO: 35ppm or CH4: 20%LEL |
High alarm level | CO: 200ppm or CH4: 50%LEL | CO: 200ppm or CH4: 50%LEL |
Signal output | 420mA Low alarm relay output High alarm relay output | RS485 |
Cable | 1.5 mm2×3 field cable | 1.5 mm2×4 field cable |
Sampling method | Diffuse naturally | |
Response time | 60s | |
Power supply | DC24V±25% | |
Consumption | 2W/channel | |
Working condition | Tem.: 2050 Hum.: ≤95% | |
Protection grade | IP66 | |
Air pressure | 86kPa106kPa | |
Weight | ≤500g | |
Dimension | L×B×H mm:165×118×62 | |