lT-XD series low voltage surge protective devices, widely applicated to low voltage power supply system(DC) protection.
Surge protection device:
technical paramters:
Specification | LT-XD6 | LT-XD12 | LT-XD24 |
Operating voltage Un(DC) | 6V | 12V | 24V |
Max operating voltage Uc(DC) | 7.5V | 15V | 28V |
Protection level Up | ≤200V | ≤220V | ≤300V |
Nominal discharge current In(8/20uS) | 5KA | ||
Max discharge current Imax (8/20uS) | 10KA | ||
Terminal connection cut-area | 1.5~6mm2 | ||
Response time (ns) | ≤25 | ||
Temperature | -40°C~ 85°C |
DIN-rail mounting (35mm), installed in the power supply terminal of the protected device with a parallel connection. N,L connect with power, PE is earth terminal,connect to the earthing busbar. With a indicator light, to show the working situation, when the light is out,means this SPD is already invalidated, must replace it.