Welcome to B2BAGE
Copper conductor XLPE insulation cable series
Copper conductor XLPE insulation cable series

Minimum Order: 0
Quality/Safety Certification: 0.00


Copper conductor XLPE insulation cable series
We have the most professional manufactory of communication cables.

Copper conductor XLPE insulation cable series H07Z-K  UL3386 

We have the most professional manufactory of communication cables.

We can produce products as your requirement.

We also accept small order.

 

Construction, Electric Properties

 

Cross sectional area

 

mm2

Construction No/sigle wire Dia.

 

/

mm

Nominal thick.of insulation

 

 

mm

Nominal overall dia.

 

mm

Maximum Ave. overall Dia.

 

mm

20 D.C. Max.resistance

20

 

Ω/km

90 Min. insulation resistance

90

 

MΩ.km

Rated voltage

 

V

1.5

30/0.25

0.76

3.1

3.3

13.3

0.01

450/750

2.5

49/0.25

0.8

3.6

3.8

7.98

0.009

450/750

4

56/0.30

0.8

4.2

4.4

4.95

0.007

450/750

6

84/0.30

0.8

5.1

5.4

3.3

0.006

450/750

10

77/0.40

1.15

6.8

7.1

1.91

0.0056

450/750

16

119/0.40

1.50

8.3

8.6

1.21

0.0046

450/750

25

189/0.40

1.53

10.2

10.6

0.78

0.0044

450/750

35

266/0.40

1.53

11.5

11.9

0.554

0.0038

450/750

 

Cable configuration

 

Insulation Color

 

Color

 

PANTONE Code

 

Chromatic aberration(E)

 

Test method

 

Red

PANTONE 193C

≤4.0

DKBA 4023-2007.10

Yellow

PANTONE 115C

≤4.0

Blue

PANTONE 3005C

≤4.0

Green

PANTONE 3282C

≤4.0

Black

PANTONE 3C

≤4.0

Brown

PANTONE 4705C

≤4.0

Gray

PANTONE 424C

≤4.0

Note: The color not mentioned should meet IEC 60304

 

Insulation Mechanical and Physical Characteristic  

 

Property

 

Iinsulation

 

Test condition

 

Before Aging

 

 

 

Tensile Strength

 

≥10.3MPa

 

Elongation

 

≥150%

 

After Aging

 

 

136±2, 168h

Tensile Strength

 

≥10MPa

 

Elongation

 

≥125%

 

Tensile Strength Variation

 

≤30%

 

 

Elongation Variation

 

≤30%

 

 

Cold Bending

 

No Crack

 

-20±2,4hrs

Cold Impact

 

No Crack

 

-15±2

Heat Shock

 

No Crack

 

136±2,1hrs

Deformation Resistance

 

≤50%

 

121±1

Flammability

 

A

IEC 60332-1A

 

Environment Requirements

 

Burning occur gas acidity PH≥4.3         IEC 60754-2

Acid gas release mounts ≤5 mg/g         IEC 60754-1

Burning release gas photic rate ≥60%       IEC 61034-2

Burning occur the conductivity value≤10μS/mm  IEC 61034-2

Meet the standard of RoHS

Ads by Google



About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.