ACSR ( Aluminum conductor steelreinforce) --Used as bare overhead transmission and as primary and secondary distribution cable. ACSR offers optimal strength for line design. Variable steel core stranding enable desired strength to be achieved without sacrificing ampacity.
Nominal cross section aluminum/steel ( mm²) | Structure (no./diameter) ( mm ) |
Outer diameter ( mm ) |
D.C.resistor at 20°c ( Ω/km ) |
Calculated breakingload(N) |
Calculated weight ( kg/km ) | |
aluminum | steel | |||||
10/2 16/3 25/4 35/6 | 6/1.50 6/1.85 6/2.32 6/2.72 | 1/1.50 1/1.85 1/1.32 1/2.72 | 4.50 5.55 6.96 8.16 | 2.706 1.779 1.131 0.8230 | 4120 6130 9290 12630 | 42.9 65.2 102.6 141.0 |
50/8 50/30 | 6/3.20 12/2.32 | 1/3.20 7/2.32 | 9.60 11.60 | 0.5946 0.5692 | 16870 42620 | 195.1 372.9 |
70/10 70/40 | 6/3.80 12/2.72 | 1/3.80 7/2.72 | 11.40 13.60 | 0.4217 0.4141 | 23390 58300 | 275.2 511.3 |
95/15 95/20 95/55 | 26/2.15 7/4.16 12/3.20 | 7/1.67 7/1.85 7/3.20 | 13.61 13.87 16.00 | 0.3058 0.3019 0.2992 | 35000 37200 78110 | 380.8 408.6 707.7 |
120/7 120/20 120/25 120/70 | 18/2.90 26/2.38 7/4.72 12/3.6 | 1/2.90 7/1.85 7/2.10 7/3.60 | 24.50 15.07 15.74 18.00 | 0.2422 0.2496 0.2345 0.2364 | 27570 41000 47880 98370 | 379.0 466.8 526.6 895.6 |
150/8 150/20 150/25 150/35 | 18/3.20 24/2.76 26/2.70 30/2.50 | 1/3.20 7/1.85 7/2.10 7/2.50 | 16.00 16.67 17.10 17.50 | 0.1989 0.1980 0.1939 0.1962 | 32860 46630 54110 65020 | 461.4 549.4 601.0 676.2 |
185/10 | 18/3.60 | 1/3.60 | 18.00 | 0.1572 | 40880 | 584.0 |