Lightning arrester or surge arrester
Lightning arrester or surge arrester

Minimum Order: 0
Quality/Safety Certification: 0.00


Power station type lighting arrester is used to protect the AC electric equipment in power plants and transformer substations

It is used to protect the AC electric equipment in power plants and transformer substations against damage of atmosheric over-voltage and operating voltage.

 

Power station type
it is used to protect the AC electric equipement in power plants and transformer substations against damage of atmospheric over-voltage and operating voltage.
Model of arresterRated voltage of systemRated voltage of arresterContinuous operating voltageDirect-current reference voltageResidual voltage under steep impulse currentResidual voltage under lighting impluse currentResidual voltage under switching impulse currentSquare-wave discharge capacityHeavy current impluse withstand capacity
KV(r.m.s)not less than KVnot more than KVAKA
HY5WZ3547.515.513.511.515065
HY5WZ61081531272315065
HY5WZ101713.62451.54538.315065
HY5WZ355140.873154134114400100
HY5WZ355443.277154134114400100
HY5WZ668467.2121254221188600100
HY5WZ669072.5130270235201600100
HY5WZ11010078145299260221600100
HY5WZ11010884157323281239600100
HY10WZ355140.873154134114400100
HY10WZ355443.277154134114400100
HY10WZ669072.5130264235201600100
HY10WZ1109676.8140280250212600100
HY10WZ11010078145280260221600100
HY10WZ11010884157314281239600100
HY10WZ220192150280560500424800100
HY10WZ220200156292582520442800100
HY10WZ220216169314628562447800100