UL PV WIRE
Specifically designed for connecting photovoltaic system components inside and outside of building and equipment.
0FENGGUO JINE SOLAR PV WIRE&CABLE meeting UL4703 requirements
1.Cable design1.1 Conductor: fine wire strands of tinned copper wires,according IEC 60228,Class 5
1.2 Insulation:Flame retardant PE,electron beam cross-linked, Colours: black
1.3 Outer jacket: Flame retardant PE,electron beam cross-linked
resistance against water , UV resistant , Jacket colour black,red
2.Temperature range
2.1 Max,temperature at conductor -40°C up to +120°C
2.2Temperature range -40°C up to +90°C(min.25 years)
3.Electrical characteristics
3.1 Nominal AC voltage 600V
3.2 AC-test-voltage 3.0KV(14AWG~10AWG)
3.5KV(≥8AWG)
3.3 Insulation-Resistance at 15.6°C 14AWG≥1165 MΩ/km
12AWG≥1000 MΩ/km
10AWG≥843 MΩ/km
8AWG ≥793 MΩ/km
4.Environmental characteristics
4.1 Sunlight-Resistance according clause 30 of UL 854
4.2 Vertical flame FT1 according clause 1100 of UL 1581
5.Product Description
AWG
Nominal Area(mm²)
Conductor Constuction
(n/mm)
600V Cable OD.(mm)
1000V~2000V Cable OD.(mm)
Conductor Max.Resistance
AT 20°C
(Ω/km)
18
0.823
TXR 16/0.254
5.10
5.85
23.2
16
1.31
TXR 26/0.254
5.50
6.25
14.6
14
2.08
TXR 41/0.254
5.90
6.65
8.96
12
3.31
TXR 48/0.300
6.40
7.15
5.64
10
5.261
TXR 105/0.254
7.20
7.95
3.546
8
8.367
TXR 168/0.254
9.00
9.50
2.23
6
13.3
TXR 266/0.254
10.10
10.60
1.403
4
21.15
TXR 420/0.254
11.50
12.00
0.882
2
33.62
TXR 665/0.254
13.30
13.80
0.5548
1
42.41
TXR 836/0.254
15.50
15.90
0.4398
1/0
53.49
TXR 1045/0.254
16.60
17.20
0.3487
2/0
67.43
TXR 1330/0.254
17.90
18.50
0.2766
3/0
85.01
TXR 1672/0.254
19.50
20.00
0.2194
4/0
107.2
TXR 2109/0.254
21.20
21.80
0.1722