ABC Cable for overhead circuit transmission
1.20 years experience
2.OEM Order taken
3.Quality assurance
ABC Cable for overhead circuit transmission
1. Rated voltage: U0/U is 1KV.
2. The long term working temperature of the conductor: the temperature of PVC and PE insulated conductor should be less then 70°C; and XLPE conductor should under 90°C.
3.The laying temperature should higher than -20.
The detail technical data of the products:
Type | Number of Cores | Section Area |
JKVS | 4 | 1-150 |
JKLVS | 3+1 | 4-150 |
JKYS JKYJS | 4 | 1-150 |
JKLYS JKLYJS | 3+1 | 4-150 |
JKVS JKYS JKYJS | 2 | 1-150 |
JKLVS JKLYS JKLYJS | 2 | 4-150 |
Core* Section area mm2 | Number of core/diameter mm | Thickness of the insulation | The resistance of the conductor at 20°C ≤Ω/km | Reference weight kg/km | |
Main core | The fourth core | ||||
3*4+1*2.5 | 1/2.25+1/1.78 | 1.0 | 1.0 | 7.41 | 48.3 |
3*6+1*4 | 1/2.76+1/2.25 | 1.0 | 1.0 | 4.61 | 95.5 |
3*10+1*6 | 7/1.35+1/2.76 | 1.0 | 1.0 | 3.08 | 141.2 |
3*16+1*10 | 7/1.70+7/1.35 | 1.2 | 1.2 | 1.91 | 215.3 |
3*25+1*16 | 7/2.14+7/1.70 | 1.2 | 1.2 | 1.20 | 289.1 |
3*35+1*25 | 7/2.52+7/2.14 | 1.2 | 1.2 | 0.868 | 382.4 |
3*50+1*35 | 7/3.00+7/2.52 | 1.4 | 1.4 | 0.614 | 526.0 |
3*70+1*50 | 19/2.14+7/3.00 | 1.4 | 1.4 | 0.443 | 655.0 |
3*95+1*70 | 19/2.52_19/2.14 | 1.6 | 1.6 | 0.320 | 886.6 |
3*120+1*95 | 37/2.03+19/2.52 | 1.6 | 1.6 | 0.253 | 1075.7 |
3*150+1*120 | 37/2.52+37/2.03 | 1.8 | 1.8 | 0.206 | 1320.8 |