JLSZW-6.10 power metering box
JLSZW-6.10  power metering box

Minimum Order: 0
Quality/Safety Certification: 0.00


imported resin, long-life
outdoor and high-accuracy
stainless steel or electrostatic spray steel box

Description 

This model combined transformer (another name is metering tank) is composed of voltage and current transformer, it is applied to three-phase circuit of AC50Hz and rated volt being 10kV or lower, to be used for volt, current and energy measuring as well as relay protection, it is suitable for urban and rural power network outdoor transformer substation in addition to kinds of volt transformer substations in industrial enterprise. Adding active and reactive energy meter onto combined transformer is named as high volt power metering tank. This product could replace oil immersed type combined transformer (metering tank).


Construction

Voltage transformer possesses indoor epoxy resin casting mechanism, its iron core is exposed, with lapping mechanism of super-quality grain-oriented cold-rolled silicon steel sheet, the primary and secondary coil are installed onto center post.

Current transformer possesses epoxy resin casting mechanism; its iron core is closed, with rolling mechanism of super-quality grain-oriented cold-rolled silicon steel sheet.

Two volt transformers (PT) and two current transformers (CT) are installed into one sealed iron box, forming one body.


Voltage transformer

Type

Rated voltage ratio(A)

Accuracy classes

Rated output (VA)

Limit output (VA)

Rated insulation level (kV)

JLSZW-6, 10

3000/100

0.2 0.5

15 30


3.6/25/40

6000/100

300

7.2/32/60

10000/100


12/42/75

Current transformer

Type

Rated voltage ratio(A)

Accuracy classes

Rated output(VA)

Rated short-time thermal current(kA)

Rated dynamic current(kA)

Rated insulation level (kV)

JLSZW-6, 10

5-200/5

0.2S

7.5

100 I 1n

2.5 I 1th

12/42/75

0.2

10

 

 

Type designation

 

 Overall Dimension

 

 Technical data

1 .Combined transformer conforms to given provisions in GB17201 -2006 <combined transformer> ;

2. Current transformer conforms to given provisions in GBI208-2006 <current transformer> ;

3. Voltage transformer conforms to given provisions in GBI207-2006 <voltage transformer> ;

4. The zinc oxide arrester must be installed at certain position with less-than-one meter distance away from product's installation place, for lightning protection.