Welcome to B2BAGE
lightning protector 15KV
lightning protector 15KV

Minimum Order: 0
Quality/Safety Certification: 0.00


lightning protector
1) 15KV, 5KA or 15KV, 10KA.
2) IEC60099; ISO9001-2000
3)Frequency of power : 48Hz--62Hz

 

lightning protector

 

1 Ambient temperature: -40 ~ +40°C

2 Altitude: not more than 2000m;

3 Frequency of power : from 48Hz to 62Hz;;

4 Earthquake intensity: not higher than 7 degrees;

5 Max wind velocity:lower than 35m/s.

 

15KV,5KA

Rated Voltage  

15 kV

Rated frequency 

48~62Hz

Continuous operating voltage

12.7 kV

Nominal discharge current

5KA

1/4 Steep current impulse residual voltage

47.5 kV

8/20 Lightning impulse residual voltage

45 kV

30/60 Switching impulse residual voltage

38.5 kV

Rectangular current withstand 2000μs 

100 A

High current withstand 4/10μs  

65kA

 

15KV,10KA

Rated Voltage  

15 kV

Rated frequency 

48~62Hz

Continuous operating voltage

12.7 kV

Nominal discharge current

10 KA

1/4 Steep current impulse residual voltage

47.5 kV

8/20 Lightning impulse residual voltage

45 kV

30/60 Switching impulse residual voltage

38.5 kV

Rectangular current withstand 2000μs 

250 A

High current withstand 4/10μs  

100 kA