lightning protector
1) 15KV, 5KA or 15KV, 10KA.
2) IEC60099; ISO9001-2000
3)Frequency of power : 48Hz--62Hz
lightning protector
1 Ambient temperature: -40 ~ +40°C
2 Altitude: not more than 2000m;
3 Frequency of power : from 48Hz to 62Hz;;
4 Earthquake intensity: not higher than 7 degrees;
5 Max wind velocity:lower than 35m/s.
15KV,5KA
Rated Voltage | 15 kV |
Rated frequency | 48~62Hz |
Continuous operating voltage | 12.7 kV |
Nominal discharge current | 5KA |
1/4 Steep current impulse residual voltage | 47.5 kV |
8/20 Lightning impulse residual voltage | 45 kV |
30/60 Switching impulse residual voltage | 38.5 kV |
Rectangular current withstand 2000μs | 100 A |
High current withstand 4/10μs | 65kA |
15KV,10KA
Rated Voltage | 15 kV |
Rated frequency | 48~62Hz |
Continuous operating voltage | 12.7 kV |
Nominal discharge current | 10 KA |
1/4 Steep current impulse residual voltage | 47.5 kV |
8/20 Lightning impulse residual voltage | 45 kV |
30/60 Switching impulse residual voltage | 38.5 kV |
Rectangular current withstand 2000μs | 250 A |
High current withstand 4/10μs | 100 kA |