Solenoid valve is widely used in automatic control and the protect circle of air-conditioning, drying machine, washing machine.
Usage:
FDF2A solenoid valve is widely used in automatic control and the protect circle of air-conditioning, drying machine and refrigeration machine.
Explanation:
Before brazing the valve body, to get rid of the coil, and protect valve body with wet cloth, and the body temperature should be below 120°C.
Orientation of installation: coil up-side, valve body 90 degree.
Working condition
Orifice,Φ7mm
Power, AC220V,AC110,DC24V,DC12V
Voltage range, 85%--110%
Frequency, 50/60Hz
Rating power, 10W
Suitable medium, R22,R134a etc
Medium temperature, -30°C~+130°C
Environmental temperature, -20°C~+50°C
Interior leak, ΔP=0.5Mpa,Q≤10ml/min
The Max working pressure, 5.0Mpa
Life, 100,000times
Temperature rise of coil, ≤80K
Specifications: