Protections:Short circuit/overload/Over Voltage
3 year warranty
UL,CB,CE certificate
MODEL | DR-45-24 | |
OUTPUT | DCVOLTAGE | 24V |
RATEDCURRENT | 2A | |
CURRENTRANGE | 0~2A | |
RATEDPOWER | 48W | |
RIPPLE & NOISE (max.) Note.2 | 480MVP-P | |
VOLTAGEADJ.RANGE | 21.6~26.4V | |
VOLTAGE TOLERANCE Note.3 | ±1.0% | |
LINEREGULATION | ±1.0% | |
LOADREGULATION | ±1.0% | |
SETUP.RISEHOLD.TIME | 800ms, 60ms/230VAC at full load | |
HOLD TIME(TYP.) | 100ms/230VAC at full load | |
INPUT | VOLTAGERANGE Note.6 | 85~264VAC 120~370VDC |
FREQUENCYRANGE | 47~63HZ | |
EFFICIENCY (Typ.) | 80% | |
AC CURRENT (Typ.) | 1.5A/115VAC 0.75A/230VAC | |
INRUSH CURRENT (Typ.) | COLD START 28A/115VAC 56A/230VAC | |
LEAKAGE CURRENT | <1Ma / 240VAC | |
PROTECTION | OVERLOAD | 105~160%rated output power |
Protection type :Constant current limiting, recovers automatically after fault condition is removed | ||
OVER VOLTAGE | 27.6~32.4V | |
Protection type:Shut off o/p voltage, clamping by zener diode | ||
OVER TEMPERATURE | Tj 135°C typically (U1) detect on heat sink of power transistor | |
Protection type:Shut down o/p voltage, re-power on to recover | ||
ENVIRONMENT | WORKING TEMP | -10~+50°C (refer to output load derating curve) |
WORKINGHUMIDITY | 20~90% RH non-condensing | |
STORAGE TEMP HUMIDITY | -20~+85°C 10~95%RH | |
TEMPCOEFFICIENT | ±0.03%(0~50°C) | |
VIBRATION | 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | |
SAFETY&EMC Note 4) | SAFETY STANDARDS | UL508, TUV EN60950-1 approved |
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | |
ISOLATIONRESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC | |
EMI CONDUCTICN& RADIATION | Compliance to EN55011, EN55022(CISPR22)classB | |
HARMONICCURRENT | Compliance to EN61000-3-2,-3 | |
EMS IMMUNITY | Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, ENV50204, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A | |
QTHERS | MTBF | 364.5Khrs min MIL-HDBK-217F(25°C) |
DIMENSION | 93*78*67mm(L*W*H) | |
PACKING | 0.31Kg 48pcs / 16.1Kg / 1.3CUFT | |
NOTE | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 °Cof ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |