Welcome to B2BAGE
smart DIN rail R3T Temperature Transmitter of thermocouple
smart DIN rail R3T Temperature Transmitter of thermocouple

Minimum Order: 0
Quality/Safety Certification: 0.00


1. smart din rail mounting temperature transmitter of thermocouple
2. 4-20 ma industrial
3. width:12mm
4. standard packaging

Description of product

R3T series temperature transmitter are used in industrial automation system, receiving thermoelemt signal from industrial on-site and transforming analog signal with corresponding temperature to DCS/PLC through isolation. It characterized by the collection and transmission of on-site industrial temperature, the matching of signal types, isolation anti-interference and stabilization of system, etc. between industrial field instruments and DCS/PLC. It contains a variety of combination forms like one-in with one-out, one-in with two-out, two-in with two-out, etc. The casing of the product is only 12mm width, which can fully satisfy the need of on-site high-density installation.

 

Input specifications

Input voltage range 

18V~30V DC

the Power of full-load

≤2W

Absolute maximum input voltage 

30VDC

the Power of no-load

/

Power reverse-phase protection

Yes

Power overload protection

Yes

Input signal specifications

Input signal range

R temperature measuring scope:--40°C ~ 1700°C

S temperature measuring scope:--40°C ~ 1700°C

K temperature measuring scope:--150°C ~ 1370°C

J temperature measuring scope:--80°C ~ 900°C

 

T temperature measuring scope:-160°C ~ 390°C

B temperature measuring scope:-320°C ~ 1820°C

E temperature measuring scope:--80°C ~ 700°C

Range of wire resistance

≥10MW

Minimum measure range

R: 600°C

S: 600°C

K: 120°C

J: 100°C

 

T: 100°C

B:780°C

E: 500°C

Cold junction compensation

internal cold end compensation

Output signal specifications

Output signal range

4~20mA,0~20mA,1~5V,0~5V,0~10V etc. output of signal type

Output signal resistance 

0/4~20mA output 0~550W    (with short circuit protection)

 

0~10mA  output 0~1100W   (with short circuit protection)

 

0/1~5V   output≥500KW  (with short circuit protection)

 

0~10V    output≥1MW   (with short circuit protection)

Fault output

output  

4~20mA

0~20mA

1~5V

0~5V

0~10V

 

input disconnection

about 23mA

about 23mA

about 5.75V

about 5.75V

about 11.5V

 

input out of lower limit

3mA

21mA

0.75V

5.25V

10.5V

 

input out of upper limit

22mA

22mA

5.5V

5.5V

11V

 

Typical application:

Signal of thermoelemt or millivolt voltage needed to be transformed into isolated general signal.

Occasion existing grounding potential difference.

Occasion existing high electromagnetic interference.

System needing DCS or PLC protection

Signal distribution in two ways.

 

If you have any queries, please feel free to contact with us.

:

Ads by Google



About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.