Room thermostat for BACnet MS/TP networks
1x0~10 VDC output or 2x0~10VDC outputs
Up to two-stage electric aux. heating
2
24 VAC±20% 50/60HZ
Electrical rating
2 Amp load per terminal
Sensor
NTC 5K
Temperature control range
5-60 (41-95)
Accuracy
±0.5 (±1) @25
Analog output
Voltage 1xDC 0V~DC 10V (for F08-LVB-A series)
2 x DC 0V~DC10V (for F08-LVB-A-D series)
Current 2 mA
Relay output
1 or 2 outputs with 2 Amp load
Protection class
IP30
Environment condition
Operating temperature: 0 50
Operating humidity: 5 ~99% RH
Storage temperature: -10 60 0C
Storage humidity: < 95%RH
BACnet interface
BACnet MS/TP with adjustable baud-rate
Display
LCD
Net Weight
280g
Dimensions
120mm(L)×90mm(W)×24mm(H)
Housing
PC/ABS plastic material with IP30 protection class
Mounting standard
Mounting on the wall, or 2×4/ 65mm×65mm pipe box
1.Room thermostat is typical used in buildings for VAV systems
2.Designed for BACnet MS/TP networks with 1x0~10 VDC output to cooling/heating air damper or
2x0~10VDC outputs to cooling and heating air dampers, also with one or two relay outputs to one
or two stages electric auxiliary heater
3.A PIC statement is supplied to be easily mapped back to a graphical user interface.
4.Self configuring / adjustable baud-rate senses the communication conditions of the current MS/TP network and match them.
5.BACnet PIC statement provided to further facilitate integration.
6.LCD can display working status such as room temperature, set point, analog output, etc. Makes reading and operating easy and accurate.
7.All models feature user-friendly setting buttons
8.Smart and enough advanced setup makes the thermostat being used in all VAV systems
9.Up to two-stage electric aux. heater control makes temperature controlling more accurate and energy-saving.
10.Large set point adjustment, the mini. and max. limit of temperature preset by end users
11.Celsius or Fahrenheit degree selectable
12.Cooling/heating mode auto changeover or manual switch selectable
13.Two parts structure and quick wire terminal blocks make mounting easily.
14.Infrared Remote Control (optional)