Dry Type Insulated Current Transformers
Minimum Order: 0
Quality/Safety Certification: 0.00
Electronic Current Transformers
1.Max Voltage:252KV
2.Rated Primary Current:300 to 4000A
3.Rated Secondary Current 5A
4.GOST
Electronic Current Transformers
1.Max Voltage:252KV
2.Rated Primary Current:300 to 4000A
3.Rated Secondary Current 5A
4.GOST
LVQB(T)-35/66/110/220 type SF6 gas insulated current transformer | |||||
Altitude | not exceed 2000m(the ones exceed 2000m shall be designed separately) | ||||
Ambient temperature | -40°C~+50°C, daily mean temperature not exceeds 30°C | ||||
Max monthly mean relative humidity | 90% | ||||
10min max average wind velocity | 35m/s | ||||
Max ice coating thickness | 10mm | ||||
Class of pollution | 3 4 Class | ||||
Max voltage of equipment | 40.5/72.5/126/252kV | ||||
Rated frequency | 50Hz | ||||
Rated primary current | 300~4000A | ||||
Rated secondary current | 1A or 5A | ||||
Secondary combination | 0.2, 0.2S, 0.5, 0.5S, 5P, TPY, TPS Class combination at random | ||||
Rated output | 0.2 class, 0.2S class, 0.5class, 0.5S class, 5P class: 20~60VA TPY class:10~20Ω | ||||
Accuracy limit condition of class TPY | a. primary time constant Tp=100ms or 60ms | ||||
b. short-circuit current direct component 100%(i.e. full migration) | |||||
c. specified working cycle: C-0.1s-0-0.5s(or 0.4s)-C-0.1s-0(guarantee all accuracy class times are 0.4s) | |||||
d. symmetrical short-circuit current multiple: 10, 15, 20 | |||||
Rated insulating level | current transformer of 35kV: 40.5/95/185kV; Current transformer of 66kV: 72.5/140/325kV; Current transformer of 110kV: 126/200/480kV; Current transformer of 220kV: 252/395/950kV | ||||
Short-time thermal current | 50-63kA, 3S | ||||
Rated peak withstand current | 125-160kA(peak) | ||||
Withstand voltage level under zero gauge pressure | 1.3 times of max working voltage of equipment | ||||
Partial discharge level | 1.2 times of max working voltage of equipment ≤5pC | ||||
Annual gas leakage rate | ≤0.5% | ||||
Water content of SF6 gas | ≤150×10-6(V/V) | ||||
Specific creepage distace of external insulation | 25mm/kV or 31mm/Kv | ||||
Static bearing load of primary terminal | 2000N~6000N | ||||
Max total mass of product | current transformer of 35kV: 450kg(thereinto mass of SF6 gas is 4kg); current transformer of 66kV: 500kg(thereinto mass of SF6 gas is 5kg); current transformer of 110kV: 450kg(thereinto mass of SF6 gas is 7kg); current transformer of 220kV: 1400kg(thereinto mass of SF6 gas is 23kg); |