Welcome to B2BAGE
20(10)kV Grade S11-M three phase oil distribution transformer
20(10)kV Grade S11-M three phase oil distribution transformer

Minimum Order: 0
Quality/Safety Certification: 0.00


20(10)kV Grade S11-M three phase oil immersed distribution transformer
Do special order according to customer design

20(10)kV Grade S11-M three phase oil immersed distribution transformer

Main Characteristics

1.Low no-load loss and energy conservation

2.Low noise and environmental protection

3.Long service lifetime and safe and reliable performance

4.Advanced structural design and exquisite craftsmanship

5.Appropriate protective measures

 

Normal Operation Conditions

1.Installation site: outdoors or indoors

2.Altitude: less than 1000M

 

3.Ambient temperature: -25oC~+40oC

 

4.Maximum relative humidity: 95%(25oC)

5.Earthquake-resistant capability: the horizontal acceleration of ground surface is 0.3g, and 

          the vertical acceleration of ground surface is 0.15g

          concurrently acting continuous three sine waves, safety factor ≥1.67

6.All-weather working capability in outdoor environment

7.The equipment has certain capability in dustproof, antifouling, waterproof, earthquake resistance and shock resistance

 

Note: Transformers operating in special environment are available upon the demand of customers.

 

Standard of Products

GB1094.1-1996, GB1094.2-1996, GB1094.3-2003, GB1094.5-2008, GB1094.7-2008, GB/T6451-2008, etc

 

20(10)kV S11-M-30~2500/20,

Performance Parameter List

 

Rated

capacity

(kVA)

Voltage combination and tap range

Connection

Group

No-load

loss

(W)

 

75°C load loss

(W)

No-load

current

(%)

Impedance

voltage

(%)

High

voltage

(kV)

Tap

(%)

Low

voltage

(kV)

50

20

(10)

±5

±2*2.5

 

0.4

Dyn11

Yyn0

300

1230

1.90

6.0

 

100

470

1980

1.50

160

580

2460

1.30

200

640

2930

1.10

250

730

3400

1.10

315

840

4060

1.00

400

1000

4820

1.00

500

1170

5760

1.00

630

1320

6800

0.80

800

1520

8220

0.80

1000

1790

9730

0.80

1250

2060

11480

0.80

1600

2410

13790

0.80

2000

2800

16290

0.60

2500

3340

19270

0.60

1600

2410

14500

0.80

8.0

2000

2800

17700

0.60

2500

3340

21000

0.60

Note: 1. Load loss values above the oblique line in the table are applicable to the Yyn0 connection group, and the values below the oblique line are applicable to the Dyn11 or Yzn11 connection group. 

         2. The list shows main performance parameters of a three-phase duplex winding off-circuit-tap-changing distribution transformer. Customized transformers of different specification are available upon the demand of users.