1.mainly for industrial applications
2.better at protection as surges,spike,blackput,shortages,outages,poor-quality supply
Model | TP820 | |
Rated capacity | 20KVA/16KW | |
Operating principle | Pure sine wave dual conversion on-line | |
AC input | Phase | Three phase +N+G |
Voltage | 220V±20% | |
Frequency | 60HZ±10% | |
DC input | Rated DC voltage | 180Vdc |
floating voltage | 200Vdc | |
Cut-off voltage | 160Vdc | |
Charging time | charge to 90% in 8 hours | |
AC output | Phase | Three phase +N+G |
Voltage | 220Vac±5%( stable load), 220Vac±5%( fluctuant load) | |
Frequency | 60Hz±0.5%(On battery) | |
Power factor | 0.8 | |
Wave-form | Sine wave | |
Total Voltage harmonics distortion | Linear load <3%; non-linear load <5% | |
Output voltage transient characteristic | ±5% ( Load abrupt change From 0 to 100%) | |
Transient response time | <20ms | |
Crest factor | 3:1 | |
Overload protection | >125%,1min;>150%,200ms | |
System spec | Full load efficiency | ≥90% |
Transfer time | 0ms | |
Protection | Overload, over charge and over discharge: phase error, out the range of voltage and frequency, over current, short circiut, over temperature ect. | |
Display | LCD and LED indicator | |
Communication | RS232 interface and SNMP card(optional) | |
Environment temperature | -5~40°C | |
Relative ambient humidity | 20~95% (Non-condensing) | |
Altitude | <1500m:1% rated capacity decrease against rised 100m | |
Cooling method | Forced air-cooling with temperature control | |
Surge protection | 10/700Us,5KV :8/20Us,20KA | |
Safety rate | IP21 | |
Noise(dB) | <55dB |