Welcome to B2BAGE
No Break - 10kva online no break(Centrio DSP 6-20KVA)
No Break - 10kva online no break(Centrio DSP 6-20KVA)

Minimum Order: 0
Quality/Safety Certification: 0.00


1.Online protection
2.Motorola Microprocessor
3.Advanced Current Control
4.IGBT power compone
5.ups manufacturer

Outstanding Feature

1. Texas Instruments DSP processor

2. Motorola Microprocessor

3. Module design

4. Advanced Current Control

5. IGBT power component

6. Power Factor Correction

7. Online Maintenance

8. High frequency and double conversion on-line technology

9. Advanced PFC technology

10. EPO Function

11. Wide input voltage range

12. Fully digitized microprocessor control

13. Parallel redundancy

14. Advanced battery management

15. Lightning and surge protection, short circuit and overload protection

16. Multilingual LCD display 

 Technical specification

MODEL

C6K(S)L

C10K(S)L

3C10KSL

3C15KSL

3C20KSL

 Power(VA/Watt)

6000VA/4200W

10000VA/7000W

10000VA/7000W

15000VA/10500W

20000VA/14000W

INPUT

Voltage & Voltage Range

220 VAC, 1 Phase + Neutral

220 VAC, 1 Phase + Neutral

380 VAC, 3 Phase + Neutral

380 VAC, 3 Phase + Neutral

380 VAC, 3 Phase + Neutral

Voltage Tolerance

176 – 276 VAC ± 3%

176 – 276 VAC ± 3%

304 – 478 VAC ± 3%

304 – 478 VAC ± 3%

304 – 478 VAC ± 3%

Power Factor

≥ 0.98

≥ 0.98

≥ 0.95

≥ 0.95

≥ 0.95

Current (nominal)

23 Ampere

37 Ampere

13 Ampere / Phase  - 39 A

23 Ampere / Phase  - 69 A

30.3 Ampere / Phase - 91 A

Input Fuse

32 A NFB

50 A NFB

63 A NFB

100 A NFB

100 A NFB

Frequency & Frequency Range

50 Hz, 46 ~ 54 Hz

Working with Gen Set

Perfect Voltage and frequency Compatibility

OUTPUT - INVERTER and BYPASS

Load Power Factor Range

0.65 inductive - 1.0 resistive

Voltage Wave Form

Sinusoidal

Voltage & Voltage Tolerance

220 / 230 / 240 VAC ± 1%

Dynamic Response

At 50% - 100 - 50% unbalanced load, max voltage decline < ± 5%

Recovery Time

At Dynamic load Changes, Output Voltage recovery time is 60 msec ± 1%

Total Harmonic Distortion

For Linear Load ≤ 2%, Non Linear Load ≤ 6%

Frequency & Frequency Range

50 Hz / Mains 46-54 Hz, Battery Mode ± 0.1% (0.05 Hz) 

Crest Factor

3:1

Over Load (Mains)

For 105% - 130% load 10 mins., for > 130% load transfer to bypass after 1 sec, shutdown after 1 min at overloaded bypass

Over Load (Battery)

At > 105% load shut down after 10 sec.

Bypass and Transfer Time

Standard static bypass, Completely Uninterrupted transfer between   Mains - Battery / Battery - Mains

Bypass Voltage Tolerance

176 – 261 VAC, 1 Phase + Neutral

BATTERY

Type and Placement

Maintenance Free, Dry Type

Nominal Battery Voltage

240 VDC

INDICATORS & CONTROL PANEL

Type

LCD Panel

Control Panel

Push Buttons (Open / Close, Audible Alarm Cancellation)

Measuring and Alarms

 % Load, Input Voltage Exist, Output Voltage Exist, Bypass Active, Battery Mode, Battery Capacity (%), Inverter in Service, Fault

Indicators (LED)

Mains On, Mains Reverse, Battery Mode, Bypass On, Load / Battery Level, Overload, Fault

PROTECTIONS

Overload

Electronic Protection is available. In case of exceeding limits, the load is transferred to bypass without any interruption

Short Circuit

Inverter shuts down automatically 

Over Temperature

If the internal Temperature is 90°C the load is transferred to bypass, When it returns < 80°C, Inverter starts to work

Modem / Network Protection

Modem / Network protection input against to Voltage Spikes

AUDIBLE ALARMS

Alarm Type and Alarms

Buzzer, it can be switched off by audible alarm button.

Battery Mode, Battery Low, UPS fault, Overload, Short Circuit, Over Charge, Charger, Bypass, Inverter fault, Communication fault

COMMUNICATION

Interface and Protocol

Standart DB 9 (Female) Port, Intelligent RS232 (standard), SNMP(optional) and DB25 parallel port (for paralelling, optional)

Software

Winpower-XP

GENERAL

Total Efficiency At 100% load

88%

Noise Level

    ≤ 55 dBA

≤ 60 dBA

Electro Magnetic Compatibility

EN 61000-4-2 (ESD), 4-3 (RS), 4-4 (EFT), 4-5 (surge), IEC 62040-2 (EMI)

Operation Temperature and Humidity

0 °C ~ 40 °C, maximum 20-90% (Non Condence)

Storage Temperature

-20 °C ~ +70 °C

Protection Class

IP20

Cooling Type

Forced cooling with variable speed fan according to load %

Operation Altitude

≤ 1000 meter (from the sea level), at nominal load

Dimensions (mm), W x H x D

260x717x570

Weight W/O / W/Battery (kg)

 35 / 84

38 / 93

 38.5

55

 55 