1, Concentration is lower than 100 mm/nm3.
2, The flue gas blackness is lower than Ringelmann level 1.

Item/parameter/ modelSCL6-1.25-AIISCL8-1.25-AIISCL10-1.25-AIISCL15-1.25-AIISCL20-1.25-AII
Rated evaporation capacityt/h68101520
Operation pressureMpa1.251.251.251.251.25
Steam temperature°C1.941.941.941.941.94
Water-inlet temperature°C2020105105105
Boiler heating efficiency%80.681.8681.1782.3482.95
Area of boiler heating surfacem2137.6175210435578
Area of stkerm27.238.611.7216.418.87
FuelCoal available Coal II,low heat capability 17700-21000KJ/KG
Consumption kg/h9001280145023403180
Dimensions of biggest parts for shipment(L*W*H)m7.83X3.34X3.468.82X3.34X3.467.1X3.4X3.59.05X3.35X3.6910.6X3.35X3.69
Primary steam valve drifted diametermmPn1.6 Dn125Pn1.6 Dn125Pn1.6 Dn125Pn1.6 Dn125 
Water inflow valve drifted diametermmPn1.6 Dn50Pn1.6 Dn50Pn1.6 Dn50Pn1.6 Dn65Pn1.6 Dn65
Weight of biggest parts for shipmentt364523/272427
Overall dimensions of boiler assembled(L*W*H)m10.4X5.33X3.4611.6X5.4X3.98X4.5X612.3X5.3X7.214.2X5.3X8.04
Tatal boiler weightt424888.69108116
Boiler feed pumpModel DB12-25X7DG12-25X7DG12-25X7DG20-35X5DG25-35X5
Vetilationkw1515152222
Blast fanModel 4-72No4.5A4-72No8.55A4-72No8.5ATG15-1TG20-1
Ventilationm3/h91949369-181379369-181372300032079
Wind pressurePa20362535-33912535-339119602559
Motor PowerKW7.518.518.518.530
Induced draft fan Model YT6-1Y6-41-13 No11.2DY6-41-13 No11.2DY250M-4Y280S-4
Ventilationm3/h2200041773-2157841773-215784000054520
Wind pressurePa36262764-36972764-369730383236
Motor Powerkw3745455575