LW36-55       outdoor high voltage AC SF6 circuit breaker
NameUnitValue
Rated voltagekV55
Rated power frequency withstand voltage(1min)To earthkVK·140
Between interrupterK·140
Rated thunder impulse withstand voltageTo earthK·325
Between interrupterK·325
Powerfrequency withstand voltage under zero gauge pressure of SF6(5min)K·84
Rated frequencyHz50
Rated currentA3150
Amplitude factor 1.5
Rated short-circuit breaking currentKA31.5
Rated short-circuit breaking current(peak)KA80
Rated short-circuit with stand currentKA31.5
Rated peak value withstand current80
Rated short-circuit durations4
Rated out-of-phase breaking currentKA8
Breaking current of close-in faultKA90%lk,75%lk
Rated line-charging breaking currentA10
Operating sequence O-0.3s-CO-180s-CO
Resistance of the main circuitμ Ω≤40
Rated gauge pressure of SF6(20°C)Mpa0.5
Minimum functional gauge pressure(20°C)Mpa0.45±0.03/0.40±0.03
Annual leakage rate of SF6 <0.5%
Amount of water of SF6(V/V)ppm≤150×10-6
Mechanical lifetimes10000
Electrical level of radio interferenceμ V≤500
Creepage distanceBetween interruptermm>1800
To earth>1800
Weight of the SF6kg6
Weight of the circuit breakerkg1000/2000(with transformer)
note:external insulation level is changed by modified coefficient. Every 2000m of altitude, K=1.13;altitude3000m, K=1.28

 

mian technical data of structure
NameUnitValue
Auxiliary circuit voltageVDC220 or DC110
Thevoltage/current of the opening and closing coilsV/ADC110/4;DC220/2
Eenergy storage motorRated voltageVDC220,AC220/DC110,AC110
The range of normal working voltageV85%-110%
PowerW600
The energy storage time of motors≤15
The loop voltage of the heater and the lampVAC220
Rated voltage of the auxiliary switchVDC220,AC220/DC110,AC110
Rated current of the auxiliary switchA10
Contacts of the auxiliary switches 10 normal opened contacts and 10 normal closed contacts

 

Mechnical adjustment of the breaker
NameUnitValue
Center distance between polesmm1500
Strode length of the moving contactmm120+30 
Contact stroke length of the moving contactmm25+20
Length of the inter phaseoperating connecting rodmm110+30
Switch-off speedm/s4.2-5m/s
Switch-on speedm/s2.2-3m/s
Switch-off timems≤40
Switch-on timems≤100
Break timems≤60
Switch-on/off timems≤80
Switch-off/on timems300
The time difference of the opening of three phasesms≤2
The time difference of the closing of three phasesms≤3

 

 

 

 

 

Order notice :

The type and the specification of hte circuit breaker .

Rated electric parameter

Environmental condition

Rated electric parameter of control loop

The connection direction of the primary upper terminal

Ads by Google



About Us | Contact Us | Help | Terms & Conditions
Hot Products: A | B | C | D | E | F | G | H | I | J | K | L | M | N | O | P | Q | R | S | T | U | V | W | X | Y | Z | 0-9
Copyright Notice @ 2008-2022 B2BAGE Limited and/or its subsidiaries and licensors. All rights reserved.