DZ47LE miniature circuit breaker
AC 230/400V Input
Pole No.1P+N,2,3P+N,4
Rated frequency: 50/60Hz
Characteristics
Protection against both overload and short circuit
High short-circuit capacity
Its frame and parts adopt plastics of high fire-resistant and shockproof
small apperance.light weight
comply with the standard IEC60898 and GB10963
General
1. Application:
Personnal and fire protection cable and line protection against overload and short circuit.
2. General rules for choosing RCBO:
a. Rated residual operating current
IΔn≤30mA: additional protection in the case of direct contact;
IΔn≤300mA: preventative fire protection in the case of ground fault currents.
b. Tripping class
AC class-Tripping is ensured for sinusoidal alternating currents, whether they be quickly applied or slowly increase.
c. Tripping curve
C curve(5-10 In)protection and control of the circuits against overloads and short-circuit; protection for resistive and inductive loads with low inrush current.
D curve(10-14 In)protection and control of the circuits against overloads and short-circuit; protection for circuits which supply loads with high inrush current at the circuit closing(LV/LV transformers, breakdown lamps).
Specification
Standard | IEC/EN 60898-1 | ||
Electrical features | Poles | P | 1P+N,2,3P+N,4 |
Type(wave from of the earth leakage sensed) |
| AC | |
Thermo-magnetic release characteristic |
| C,D | |
Rated current In | A | 6,10,16,20,25,32,40,50,63 | |
Rated voltage Ue | V | 230/400 | |
Rated sensitivity IΔn | A | 0.03,0.05,0.1,0.3 | |
Rated residual making and breaking capacity lΔm | A | 500(ln≤63A)630(ln=63A) | |
Rated short-circuit capacity Icn | A | 3000/4500 | |
Break time under IΔn | s | ≤0.1 | |
Rated Impulse withstand Voltage(1.2/50)Uimp | V | 4000 | |
Dielectric Test Voltage at ind.Freq.for 1min | Kv | 2 | |
Insulation voltage Ui | V | 500 | |
Pollution Degree |
| 2 | |
Mechanical features | Electrical Life | t | 2000 |
Mechanical Life | t | 2000 | |
Protection Degree |
| IP20 | |
Ambient Temperature (with daily average ≤35°C) | °C | -5~+40 | |
Storage Temperature | °C | -25~+70 | |
Installation | Terminal Connection Type |
| Cable/U-type busbar/Pin-type busbar |
Terminal Size Top/Bottom for Cable | mm2 | 25 | |
AWG | 18-3 | ||
Terminal Size Top/Bottom for Busbar | mm2 | 25 | |
AWG | 18-3 | ||
Tightening Torque | N*m | 2 | |
In-lbs | 18 | ||
Mounting |
| On DIN rail EN60715(35mm)by means of fast clip device | |
Connection |
| From top |
Temperature Derating
Please refer to table below for temperature compensation correction
Temperature | -15°C | -5°C | 0°C | 10°C | 20°C | 30°C | 40°C | 55°C |
Temperature compensation coefficient | 1.19 | 1.15 | 1.13 | 1.06 | 1.05 | 1.00 | 0.96 | 0.89 |