co2 controller with temp.&RH%
co2 controller with temp.&RH%
Tongdy [China]

Model No: F2000IAQ-CO2-30XX/50XX
Place of Origin: Beijing,China
Brand Name: Tongdy
Packaging: Full and firm package
Minimum Order: 100pcs
Quality/Safety Certification: CE

¨   Features

u Multiple functions and high performance with low prices
u Wall mounting type and duct type selectable
u LCD display detecting both CO2 level and temperature, also relative humidity (optional)
u NDIR infrared CO2 module inside with special ABC Logic Self Calibration System. It makes the CO2 measurement more accurate and more reliable in use.
u 15 years lifetime of CO2 sensor
u Microprocessor control, quick response, high precision
u Provide up to three 0~10VDC outputs or relay dry contact outputs, or up to three mix outputs.
u The analog output with two alternatives: linearized over full range output or PID control output
u Different control mode for delays can be selected by user’s application, for example for ventilation or for greenhouse or other applications.
u Locale adjustable range of CO2: 0~20,000ppm or 0~50,000;
u Modbus RS-485 communication interface optional, 15KV antistatic protection, independent base address setting
u CE-Approval

 
 
¨   Application
F2000IAQ-CO2 monitor/controller is used to monitoring and control room CO2 level, as well as room temperature and humidity, provide one or two or three 0~10VDC analog outputs and up to three dry contact outputs . F2000IAQ-CO2 can be as a programmable logical controller to control CO2 level, temperature or humidity, and also as a transmitter DDC/PLC controller or other automation systems. It provides a RS485 communication interface with an independent address to PC or other control systems.
u   Hotel, exhibition hall, hospital, shop, restaurant, air port, train station, theater and other public places
u   House, villa, office, meeting room, classroom and other places
u   Greenhouse, mushroom, grown room and other agricultural applications
u   All ventilation systems
 
 
 
 
 
 
 
 
 
 
 
 
¨ Buttons and LCD
 

CO2measurement
analog output
humidity
room temperature
 
relay turns on
lock mode
decrease
turn on/off
increase
switch setting
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

¨   Specifications
 
Gas detected
Carbon Dioxide (CO2)
Sensing element
Non-Dispersive Infrared Detector (NDIR)
Temperature sensor
NTC
Humidity sensor
HS series capacitive sensor
Temperature dependence
0.2% FS/℃
Temperature correction
Self compensation
Power supply
24VAC/VDC, or 100~240VAC, 60HZ, selectable with the order
Consumption
3.5 W max. ; 2.5 W avg.
Accuracy@25℃(77℉)
±30ppm + 3% of reading
Stability
<2% of FS over life of sensor (15 yr typical)
Calibration interval
ABC Logic Self Calibration Algorithm
Non linearity
<1% of FS
Pressure dependence
0.13% of reading per mm Hg
Altitude calibration
Programmable from 0-9,900m in 100m increments
Response Time
<2 minutes for 90% step change
Signal update
Every 2 seconds
Warm up time
2 hours (first time)
2 minutes (operation)
CO2 measuring range
0~2,000ppm (default)
0~20,000ppm, programmable selection
0~50,000ppm
CO2 setting & Display resolution
1ppm
Temperature measuring/ setting range
0~50℃(32~122℉)/ 5~45℃(41~113℉)
 
 
 
Humidity measuring/setting range
0~99%RH/ 5~95%RH
Analog output
0~10VDC linearized output or PID control output, selectable by end users
Output resolution
10Bit
Relay output
One or two dry contact outputs with programmable selection to control CO2, temperature, humidity
Rated switching current: 3A(220VAC/30VDC), resistance load
Communication interface
RS-485, 9600/14400/19200(default)/28800 or 38400bps (programmable selection), 15KV antistatic protection, 3 independent base address, max network node 64
Flow rates
Diffusion version 80 ~ 120 cc/min
Flow through version 40~50cc/min
Operation conditions
0~50℃(32~122℉); 0~95%RH,
Storage conditions
10~50℃(50~122℉)/ 20~60%RH non condensing
NDIR life
15 years
Weight
360g
Dimensions
130mm×90mm×40mm
Installment standard
65mm×65mm or 2”×4”wire box
Interface connections
Maxi. 9 terminals
Wiring standard
wire section area<1.5mm2
Approval Standard
CE-Approval
Programming and selection
Via internal jumpers and push-buttons on the panel
 
 
¨ Models Guide
 
F2000IAQ-CO2- X1 X2 Y1 Y2- RH- Z
     
X1 (the product type)
  3- CO2 and temperature detection
      5- CO2 and temperature detection with Modbus RS-485 communication
 
X2 (display type)
0-LCD display
1-LCD display with 3 LED lights beside
2-Backlit LCD display
 
Y1 (Analog output)
0-no analog output
1- 1 X 0 – 10 VDC output
2- 2 X 0 – 10 VDC outputs
3- 3 X 0 – 10 VDC outputs
 
 
 
 
 
Y2 (Dry contact output)
 0- no dry contact output
1- 1 relay dry contact output
2- 2 relay dry contact outputs
3- 3 relay dry contact outputs
 
RH (Humidity detection and display)
         No RH option indicates no humidity detection and display
 
Z (power supply)
      C- 24VAC/VDC
      D- 100~240VAC (just for IAQ-CO2-300Y2/500Y2)
 
Example: F2000IAQ-CO2-3011 indicates that it can detect CO2 and temperature with one analog output and one relay dry contact output. F2000AQ-CO2-5002-RH indicates that it can detect CO2 and temperature and humidity with two relays dry contact outputs, and Modbus RS485 communication