Meanwell DRP-480S-24 Switching power supply
High efficiency 89% and low dissipation
Cooling by free air convection
MODEL | DRP-480S-24 | |
OUTPUT | DCVOLTAGE | 24V |
RATEDCURRENT | 20A | |
CURRENTRANGE | 0~20A | |
RATEDPOWER | 480W | |
RIPPLE & NOISE (max.) Note.2 | 120MVP-P | |
VOLTAGEADJ.RANGE | 24~28V | |
VOLTAGE TOLERANCE Note.3 | ±1.0% | |
LINEREGULATION | ±0.5% | |
LOADREGULATION | ±1.0% | |
SETUP.RISEHOLD.TIME | 1200ms, 40ms/230VAC,115VAC at full load | |
HOLD UP TIME (Typ.) | 23ms/230VAC,115VAC at full load | |
INPUT | VOLTAGERANGE Note.6 | 90 ~ 132VAC/180 ~ 264VAC by switch 254 ~ 370VDC |
FREQUENCYRANGE | 47~63HZ | |
POWER FACTOR (Typ.) | 0.7/230VAC only | |
EFFICIENCY (Typ.) | 89% | |
AC CURRENT (Typ.) | 8A/115VAC 3.2A/230VAC | |
INRUSH CURRENT (Typ.) | COLD START 27A/115VAC 45A/230VAC | |
LEAKAGE CURRENT | <3.5mA / 240VAC | |
PROTECTION | OVERLOAD | 105~150%rated output power |
Protection type : Constant current limiting, recovers automatically after fault condition is removed | ||
OVER VOLTAGE | 30~36V | |
Protection type : Shut down o/p voltage, re-power on to recover | ||
OVER TEMPERATURE | 100±5 (TSW : Detect on heatsink of power switch) | |
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down | ||
ENVIRONMENT | WORKING TEMP | -20~+70 (refer to output load derating curve) |
WORKINGHUMIDITY | 20~90% RH non-condensing | |
STORAGE TEMP HUMIDITY | -40~+85, 10~95%RH | |
TEMPCOEFFICIENT | ±0.03%(0~50) | |
VIBRATION | Component:10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | |
SAFETY&EMC Note 4) | SAFETY STANDARDS | UL508, UL60950-1, TUV EN60950-1 approved |
WITHSTAND VOLTAGE | I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | |
ISOLATIONRESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC | |
EMI CONDUCTICN& RADIATION | Compliance to EN55011 (CISPR11), EN55022 (CISPR22), EN61204-3 Class B | |
HARMONICCURRENT | Compliance to EN61000-3-2,-3 | |
EMS IMMUNITY | Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A | |
QTHERS | MTBF | 187.9Khrs min MIL-HDBK-217F(25) |
DIMENSION | 227*125.2*100mm(L*W*H) | |
PACKING | 2.6Kg; 6pcs / 16.6Kg / 1.75CUFT | |
NOTE | 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |